Page 28 of 51
SK2018 GLOBAL FDLA-V/P-AC-001
Control Logics for 2-Pipe System
D.4.1.
With Valve Configuration
COOL MODE
a)
MTV2, AUX1 and electric heater are always off.
b)
If Tr ≥ Ts
+ 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated and MTV1 and AUX2 are
turned on. Indoor fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated and MTV1 and AUX2 are turned off. Indoor fan runs at set speed.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV1 requires 30 seconds before it is fully open.
g)
When turned off, MTV1 requires 120 seconds before it is fully closed.
h)
When the unit is turned off, the indoor fan will shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1
≤ 2 ºC for 2 minutes, then MTV1 and AUX2 are turned off. If indoor
fan is set for low speed, then it will run at
medium speed. If it is set at medium or high speed, then it will keep running at the same speed.
b)
If Ti1 ≥
5ºC for 2 minutes, then MTV1 and AUX2 are turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Heat mode without electrical heater
a)
MTV2, AUX2 and electric heater are always off.
b)
If Tr
≤
Ts - 1 ºC (or - 4ºC if economy contact is activated), then heat operation is activated and MTV1 and AUX1 are
turned on. Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and MTV1 and AUX1 are turned off. Indoor fan repeatedly runs at low fan
speed for 30 seconds and then stops for 3 minutes.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV1 requires 30 seconds before it is fully open.
g)
When turned off, MTV1 requires 120 seconds before it is fully closed.
Heat mode with electrical heater as booster
a)
MTV2 and AUX2 are always off.
b)
If Tr
≤
Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and MTV1 and AUX1 are turned
on. Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and MTV1 and AUX1 are turned off. Indoor fan repeatedly runs at low fan
speed for 30 seconds and then stops for 3 minutes.
d)
If Ti1 < 40ºC, then the electrical heater is turned on. If 40
ºC ≤ Ti1 <
45ºC, then the electrical heater maintains its original
state. If Ti1 ≥
45ºC, then the electrical heater is turned off.
e)
The range of Ts is 16 - 30ºC
f)
Indoor fan speed can be adjusted to low, medium, high and auto.
g)
When turned on, MTV1 requires 30 seconds before it is fully open.
h)
When turned off, MTV1 requires 120 seconds before it is fully closed.
Heat mode with electrical heater as primary heat source
a)
MTV1, MTV2, and AUX2 are always off
b)
If Ti2 ≤ 30ºC (or Ti2 is damaged or disconnected), AND if Tr ≤ Ts
-1ºC (or -4ºC if economy contact is activated), heat
operation is activated, electrical heater and AUX1 are turned on. Indoor fan runs at set speed.
c)
If Tr > Ts, then heat operation is terminated and the electrical heater and AUX1 are turned off. Indoor fan repeatedly
runs at low fan speed for 30 seconds and then stops for 3 minutes.
d)
The range of Ts is 16-30 ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Содержание FDLA-09
Страница 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Страница 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Страница 53: ...FDHD V P AC MOTOR...
Страница 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Страница 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Страница 76: ...Configuration Settings D 3...
Страница 111: ......
Страница 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Страница 140: ...Page 28 of 77 SK2019 FCSD H V P ECM 001 For 2 pipe system with modulating valve For 4 pipe systems with modulating valve...
Страница 190: ...SK2019 FCSD H V P ECM 001...
Страница 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Страница 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Страница 231: ...Page 41 of 59 SK2015 SWC V EC 001 D 3 4 Unit Network Wiring Scheme Wiring diagram for a master slave network connection...
Страница 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Страница 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Страница 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Страница 250: ...FSTD C V P ECM MOTOR...
Страница 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...
Страница 278: ...Page 29 of 73 SK2015 FSTDC V P ECM 001 C 2 Wiring Diagram SK NCPFWB 001 ECM S Configuration Full Control PCB...
Страница 305: ...Page 56 of 73 SK2015 FSTDC V P ECM 001 E 4 Wiring Diagrams E 4 1 Standard Unit Wiring Diagram of SK NCPFWB 002 ECM...
Страница 322: ...Page 73 of 73 SK2015 FSTDC V P ECM 001...