IOM 1210-1 • MAGNITUDE

®

 MODEL WMC CHILLERS 

58 www.DaikinApplied.com

Building Automation 

Systems (BAS) 

All MicroTech

®

 II controllers with Open Choices

 are 

capable of BAS communications, providing easy integration 

and comprehensive monitoring, control, and two-way data 

exchange with open standard protocols such as LonTalk

®

Modbus

®

 or BACnet

®

.

Daikin Applied unit controllers strictly conform to the 

interoperability guidelines of the LonMark

®

 Interoperability 

Association and BACnet

®

 International. They have received 

LonMark

®

 certification with optional L

on

W

orks

®

 communication 

module.

Protocol Options

The following protocol options are available:

•  BACnet

®

 MS/TP

•  L

on

W

orks

®

•  BACnet

®

 IP

•  Modbus

®

 RTU

•  BACnet

®

 Ethernet

The BAS communication module can be ordered with the 

chiller and factory-mounted or can be field-mounted at any time 

after the chiller unit is installed. Connection to the chiller for all 

BAS protocols will be at the unit controller. An interface card, 

depending on the protocol being used, will have been factory 

installed in the unit controller if so ordered, or it can be field 

installed.
If an interface module was ordered, the appropriate BAS 

interface installation manual was shipped with the unit. If 

necessary, contact your local Daikin Applied sales office for a 

replacement manual or obtain one from

 

www.DaikinApplied.

com

. These documents can be easily found on the website 

using the “Search Literature” feature.

Use with On-Site Generators

Magnitude

®

 Model WMC chillers have their total tonnage 

divided between the number of compressors on the chiller. 

The compressor(s) are operated with variable frequency 

drives and if the unit has two compressors, the compressors 

start sequentially. These features make Magnitude

®

 chillers 

especially appropriate for use in applications where they may 

be required to run with on-site electrical generators. This is 

particularly true when the generators are used for temporary 

power when the utility power is lost.

Generator Sizing

Gas and diesel generators are sensitive to the compressor’s 

locked-rotor characteristics when the chillers start up. Use the 

electrical data supplied with the performance output sheet, 

obtained from the Daikin Applied sales office, for generator 

sizing purposes. The chiller data sheet will show the RLA, 

which is for each compressor. Refer to Electrical Data to 

determine the LRA, which is based on the RLA. It is important 

to size the generator to handle the LRA at startup.

 WARNING

Generator must be sized by an electrical engineer familiar 

with generator applications.

Transfer Back to Grid Power

Proper transfer from stand-by generator power back to grid 

power is essential to avoid compressor damage.

 WARNING

Stop the chiller before transferring supply power from the 

generator back to the utility power grid. Transferring power 

while the chiller is running can cause severe compressor 

damage.

The necessary procedure for reconnecting power from the 

generator back to the utility grid is as follows: 

1. 

Set the generator to always run five minutes longer than 

the unit start-to-start timer, which can be set from two to 

sixty minutes. The actual setting can be viewed on the 

OITS on the TIMERS Setpoint Screen (see 

Figure 28 on 

page 28

).

2. 

Configure the transfer switch provided with the 

generator to automatically shut down the chiller before 

transfer is made. The automatic shut-off function can 

be accomplished through a BAS interface or with the 

“remote on/off” wiring connection shown in 

"Figure 13: 

Controller Box Wiring" on page 14

.

It is not necessary to shutdown the chiller if pumps are not 

directly controlled by the chiller. Doing so, however, provides a 

more coordinated restart.
A start signal can be given anytime after the stop signal since 

the three-minute start-to-start timer will be in effect.

Содержание WMC

Страница 1: ...ion and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers Model WMC C Vintage 125 to 400 Tons 440 to 1400 kW HFC 134a Refrigerant 50 60 Hz IOM 1210 1 Group Chiller Part Number IOM1210...

Страница 2: ...peration 20 Operator Responsibilities 20 Operator Schools 20 Sequence of Unit Operation 20 Unit Enabling Disabling 20 Operator Interface Touch Screen OITS 21 The Controller 48 Building Automation Syst...

Страница 3: ...Code and local codes See Note 4 Condenser pump starting relay CP1 2 installed and wired See Note 3 Miscellaneous Yes No N A Initials Oil cooled water piping complete Units with water cooled oil cooler...

Страница 4: ......

Страница 5: ...rvice work Never unplug any cables circuit board terminal blocks or power plugs while power is applied to the panel NOTICE This equipment generates uses and can radiate radio frequency energy If not i...

Страница 6: ...lation and increasing reliability Necessary equipment protection and operating controls are included All Daikin Applied centrifugal chillers must be commissioned by a factory trained Daikin Applied se...

Страница 7: ...icroTech II unit controller is to acquire and process data relating to chiller operation issue instructions to various components of the chiller and maintain controlled operation of the chiller As a p...

Страница 8: ...t also be capable of supporting 1 5 times the shipping weight of the unit If a knockdown option was ordered on the unit reference the Knockdown Installation Manual for more information Nameplates Ther...

Страница 9: ...mm Width in mm Height in mm Shipping Weight lb kg WMC125S E2209 C2009 134 3 3411 43 5 1105 81 0 2057 5086 2307 WMC145S E2209 C2009 134 3 3411 43 5 1105 81 0 2057 5586 2534 WMC145D E2209 C2009 134 3 34...

Страница 10: ...f welding is performed on a vessel shell or tube sheet The water heads can be interchanged end for end so that the water connections can be made at either end of the unit If this is done use new head...

Страница 11: ...Operation Another condenser control method is to use a modulating two way control valve located on the outlet connection of the condenser The valve will be nearly closed at startup to restrict water...

Страница 12: ...connectors Remove plastic shipping plugs if installed from the inside of the valves prior to making pipe connections Whenever vent piping is installed the lines must be in accordance with local code r...

Страница 13: ...nd licensed electricians must perform wiring An electrical shock hazard exists that can cause severe injury or death The field power wiring required varies depending on unit model See Figure 12 Wiring...

Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index...

Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...

Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring...

Страница 17: ...MPERS WJ1 AND WJ2 MUST ONLY BE CONNECTED TO TERMINAL BLOCK 33 CHILLER FACTORY ASSEMBLY IF OPTIONAL GFP1 IS USED THEN REMOVE JUMPER WJ1 OTHERWISE COMPLETE CONNECTION WJ1 TO TERMINAL BOLOCK 38 IF OPTION...

Страница 18: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 16 www DaikinApplied com Installation Figure 14 Power Box Single and Multi Point Wiring...

Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...

Страница 20: ...other or to B or C vintage chillers consult a Daikin Applied service representative WMC chillers cannot be pLAN interconnected with WSC WDC WCC or WME centrifugal chillers Long Term Storage This infor...

Страница 21: ...trols wired Wiring complies with National Electrical Code and local codes See Note 4 Condenser pump starting relay CP1 2 installed and wired See Note 3 Miscellaneous Yes No N A Initials Oil cooled wat...

Страница 22: ...ion and impeller speed Maximum capacity at a given operating condition can be found either when the compressors have reached their maximum speed limit Mechanical limitation or when the compressors hav...

Страница 23: ...n a similar manner as the Unit Switch If the Control Source on the OITS MODES Setpoint Screen is set to Local press the STOP button on the OITS to disable the chiller This method of disabling will cau...

Страница 24: ...tails For more information on alarms see page 42 through page 47 II Information Chilled water setpoint ACTIVE LWT SETPOINT Entering and leaving evaporator water temperatures Entering and leaving conde...

Страница 25: ...creen Figure 49 on page 41 and the Alarm History Screen Figure 50 on page 42 VIEW button Shows details about the unit status and conditions Pressing this button will toggle between the Home View Scree...

Страница 26: ...Use the COMP button to toggle between the two compressors data Many of the inputs and outputs shown in the Compressor Inputs Outputs Information will also appear under the Compressor State Information...

Страница 27: ...O Unit I O EVAP or COND buttons will display the same information as what is available from the Detail View Screen Reference the Information figures in the Detail View Screen section starting on page...

Страница 28: ...will toggle to the Service Screen shown in Figure 47 on page 40 A typical Setpoint Screen is displayed in Figure 26 below Figure 26 A Typical Setpoint Screen Figure 26 shows the WATER Setpoint Screen...

Страница 29: ...urn green 7 Setpoints with numeric values can be changed in two ways Select the desired value by pressing the numbered buttons on the Numeric Keypad Press ENTER to enter the value or CANCEL to cancel...

Страница 30: ...interlock confirmation from compressor Stop Start Timer 3 3 min 3 to 20 min M Time from when compressor stops to when it can restart Start Start Timer 2 40 min 15 to 60 min M Time from when compresso...

Страница 31: ...P7 at start Surge Temperature Limit 7 50 F 2 to 45 F T At start Surge Temp ST is compared to this SP Alarm at ST 2x SP High Discharge Temp Stop 6 190 F 120 to 240 F T Max discharge temp to shut down c...

Страница 32: ...Minimum Start Position 8 10 0 to 100 T Initial position of valve when condenser EWT is at or below Setpoint 9 Stage Down 7 20 0 to 100 T Valve position below which the fans can stage down Tower Setpo...

Страница 33: ...8 70 F 40 to 120 F M Temperature for fan stage 1 on Stage Differential Lift 7 6 0 psi 1 0 to 20 0 psi M Fan staging deadband with Setpoint 1 Lift Stage Differential Temp 6 3 0 F 1 0 to 10 0 F M Fan st...

Страница 34: ...ature vs Fan Stages II VALVE SP This control strategy is tower staging up to four stages with a low limit controlled bypass valve The tower fans are controlled as in I plus a tower bypass valve is con...

Страница 35: ...r fan control with a VFD and bypass valve control See Figure 40 and Figure 41 Figure 40 TOWER Setpoint SP2 V VALVE SP VFD STAGE Figure 41 V VALVE SP VFD STAGE Percent vs Temperature As shown in Figure...

Страница 36: ...Daikin Applied startup technician Setup instructions for each of the five tower control strategies are provided next I NONE Tower Fan Staging Only This is the default setting but it is NOT a recommend...

Страница 37: ...dealing with system fluid mass component size and other factors affecting the reaction of the system to control inputs To avoid possible equipment damage these setpoints should be set by personnel ex...

Страница 38: ...itial load point RLA set in SP 5 to 100 RLA Initial Soft Load Limit 6 40 10 to 100 M Initial amps as of RLA Uses SP4 6 Soft Load Enable 5 OFF OFF ON M Soft load on or off Uses SP6 7 Nameplate RLA 4 De...

Страница 39: ...ps setpoint over the amount of time specified by the Soft Load Ramp setpoint If the amp draw rises above the currently active soft load limit value the unit will inhibit capacity increases If the amp...

Страница 40: ...one compressor on each unit Pump starts all compressors on one chiller first Standby uses this compressor only if another fails Maximum Compressors ON 10 1 1 8 M Total number of compressors allowed to...

Страница 41: ...Reset Delta T 8 10 0 F 0 0 to 20 0 F M Sets the evap delta T above which Return reset begins LWT Reset Type 7 NONE NONE RETURN 4 20mA M Select reset type NONE for none RETURN for resetting chilled wa...

Страница 42: ...creen Figure 47 is accessed by pressing the SET button from any SET screen In other words it is the second SET screen While containing information and activity buttons for the service technician it al...

Страница 43: ...e HISTORY button at the bottom of any screen that contains this button The HISTORY button will toggle between the Trend History Screen and the Alarm History Screen discussed next Figure 49 Trend Histo...

Страница 44: ...via USB In order to download the trend or alarm history first insert a USB drive into the left side of the OITS PC see Figure 3 on page 5 if help is needed to identify the OITS PC The OITS PC will ha...

Страница 45: ...history files are saved from the OITS PC as csv files These files can be opened on a normal PC and manipulated using Microsoft Excel for personal use If tech support is requested the original un mani...

Страница 46: ...1 COMPR STOP Motor Current Low Auto clears Low Motor Current Comp 2 COMPR STOP Motor Current Low Auto clears No Condenser Water Flow COMPR STOP Condenser Water Flow Loss Auto clears No Compressor Stop...

Страница 47: ...f Tripped 3x in 50 min High Discharge Temperature Circuit 1 COMPR STOP Discharge Temperature High Auto clears Locked off if Tripped 3x in 50 min High Discharge Temperature Circuit 2 COMPR STOP Dischar...

Страница 48: ...Warning Alarms Description OITS Alarm Message Alarm Reset Entering Condenser Water Temperature Sensor Fault NO ACTION Condenser EWT Out of Range Auto clears Entering Evaporator Water Temperature Senso...

Страница 49: ...rt shown on OITS panel No Alarm Re Start Fault No Alert shown on OITS panel No Alarm Re Start Fault Circuit 1 No Alert shown on OITS panel No Alarm Re Start Fault Circuit 2 No Alert shown on OITS pane...

Страница 50: ...have sub screens located under them There are two ways to navigate the menu matrix Hierarchical and Scrolled Menu Structure Hierarchical The hierarchical menu structure allows the operator to use shor...

Страница 51: ...the screens are arranged logically in a matrix as shown in Table 19 on page 50 In the scroll mode there will be a blinking cursor located at the top left of the screen The controller holds memory duri...

Страница 52: ...0 000 0 SatCond 000 0 000 0 VIEW COMP 2 6 psi F SatEvap 000 0 000 0 SatCond 000 0 000 0 VIEW COMP 7 Hours 00000 x10 Starts 00000 VIEW COMP 2 7 Hours 00000 x10 Starts 00000 VIEWCOMP 8 HWLok Interlock...

Страница 53: ...ne Valve Type NC I I v SET UNIT SPs 5 Rest Type NONE MaxResetDT 00 0 F StrtResetDT 10 0 F SET COMP SPs 5 Lead Staging 030 Nom Capacity 0100T HG Bypass 30 RLA SET COMP 2 SPs 5 Nom Capacity 0100T HG Byp...

Страница 54: ...ethods will cause the following screen to be displayed The gray background indicates where the blinking cursor will be The second row will say either Enter Operator Enter Manager or Enter Technician d...

Страница 55: ...bling see Unit Enabling Disabling on page 20 Clearing Alarms If the LEFT arrow key on the controller turns red it is an indication that there is an alarm Alarms can be cleared from the unit controller...

Страница 56: ...he range of the input NOT the operating range of the chiller Table 21 Controller Digital Inputs Description Signal Signal 1 Unit OFF Switch 0 VAC Stop 24 VAC Auto 2 Remote Off Enable 0 VAC Stop 24 VAC...

Страница 57: ...the password that must be active in order to change the setpoint The letters in the Password column refer to the following O Operator the password number for operator level is 100 M Manager the passw...

Страница 58: ...Time 5 min 1 to 60 min T Stage Differential Temp 3 0 F 1 0 to 10 0 F T Stage Differential Lift 6 0 psi 1 0 to 20 0 psi T Stage 1 On Temp 70 F 40 to 120 F T Stage 2 On Temp 75 F 40 to 120 F T Stage 3...

Страница 59: ...0 psi 0 to 20 0 psi T Tower Reset Lift 5 0 F 0 to 10 0 F T Sensor Selection ECWT B3 ECWT B3 provided or EHRT B9 not provided T Alarms Evaporator Freeze 34 0 F 9 0 to 45 0 F T Condenser Freeze 34 0 F 9...

Страница 60: ...hey may be required to run with on site electrical generators This is particularly true when the generators are used for temporary power when the utility power is lost Generator Sizing Gas and diesel...

Страница 61: ...standard waterboxes follows only qualified service personnel should perform these tasks After draining water remove all but two head bolts at roughly 10 and 2 o clock Loosen the remaining two bolts to...

Страница 62: ...D Perform MicroTech II check log and last fault analysis X III Condenser A Confirm correct water flow and pressure drop O X B Confirm appropriate water treatment O C Clean and Leak Test condenser tube...

Страница 63: ...revious value over a rolling one minute interval Error In the context of this manual Error is the difference between the actual value of a variable and the target setting or setpoint Evaporator Conden...

Страница 64: ...er s run status is continuously stored in battery backed RAM When power is returned to the compressors it checks the status of this function and if enabled it then checks if the chiller was running wh...

Страница 65: ...uction superheat is calculated for each circuit using the following equation Suction Superheat Suction Temperature Evaporator Saturated Temperature VDC Volts Direct Current sometimes noted as vdc VFD...

Страница 66: ...0 94 112 0 134 210 5 16 15 7 56 52 4 96 115 9 136 216 6 18 17 1 58 54 9 98 120 0 138 222 8 20 18 4 60 57 4 100 124 1 140 229 2 22 19 9 62 60 0 102 128 4 142 235 6 24 21 3 64 62 7 104 132 7 144 242 2 2...

Страница 67: ......

Страница 68: ...s sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied...

Отзывы: