www.DaikinApplied.com 55
IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
o
peraTIon
Table 23: Controller, Digital Outputs
#
Description
Load
Output OFF
Output ON
1
Evaporator Water Pump #1
Pump Contactor
Pump OFF
Pump ON
2
Evaporator Water Pump #2
Pump Contactor
Pump OFF
Pump ON
3
Condenser Water Pump #1
Pump Contactor
Pump OFF
Pump ON
4
Condenser Water Pump #2
Pump Contactor
Pump OFF
Pump ON
5
Tower Fan #1
Fan Contactor
Fan OFF
Fan ON
6
Tower Fan #2
Fan Contactor
Fan OFF
Fan ON
7
Expansion Valve Calibration
Digital Input (50K Ohms)
Normal
Calibration
8
Alarm
Alarm Indicator
Alarm OFF
Alarm ON
9
Tower Fan #3
Fan Contactor
Fan OFF
Fan ON
10
Tower Fan #4
Fan Contactor
Fan OFF
Fan ON
11
Alarm Output
User Defined
Alarm OFF
Alarm ON
Controller Setpoints
Table 24
groups setpoints that relate to the entire unit operation and are stored in the controller. Standard settings are made
through the OITS. The Password (PW) column indicates the password that must be active in order to change the setpoint. The
letters in the Password column refer to the following:
O
= Operator (the password number for operator level is 100)
M
= Manager (the password number for manager level is 2001)
T
= Technician (the password number for technician level is only provided to Daikin Applied technicians)
Table 24: Controller Setpoints
Description
Default
Range
PW
Unit
Unit Enable
OFF
OFF, ON
O
Control Source
SWITCHES
Switches, Local (Touch Screen), BAS Network
O
Display Units
°F/psi
°F/psi, °C/kPa
O
Language
ENGLISH
ENGLISH, (TBD)
O
BAS Protocol
Modbus
NONE, BACnet, LonWorks, Modbus
M
Motor Amps
Demand Limit
OFF
OFF, ON
M
Minimum Amps
3%
1 to 80%
M
Maximum Amps
100%
10 to 100%
M
Soft Load
OFF
OFF, ON
M
Begin Amp Limit
20%
10 to 100%
M
Soft Load Ramp
5 min
1 to 60 min
M
Maximum Rate
1.0 °F/min
0.1 to 5.0 °F/min
M
Minimum Rate
0.4 °F/min
0.1 to 5.0 °F/min
M
Staging
Mode
Pump
Normal, Efficiency, Pump, Standby
M
Sequence #
1
1,2, … (# of Compressors)
M
Maximum Compressors ON
2
1-16
M
Stage Delta T
1.0 °F
0 to 9.9 °F
M
Nominal Capacity
100 Tons
0 to 2000 Tons
T
NOTE:
Table 24
continues onto the following pages.
Содержание WMC
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...
Страница 67: ......