30
TM-RHR-1214-A
By means of pressure readings :
By Means Of Diagnosis Flow Chart
Generally, there are two kinds of troubles, i.e. starting failure and insufficient cooling.
“Starting Failure” is caused by electrical defect while “Insufficient Cooling” is caused by
improper application or defects in refrigerant circuit.
I) Diagnosis Of Electric Circuit
No Cooling
Unit fail to start
Check power supply
- voltage
- phase
- frequency
Check settings of remote control box
Compressor fails to start
Check circuit breake & fuse
Check power source cord
Fan fails to start
Fan Motor Capacitor defective
Loose Connections,
Contactors
Irregular motor resistance ( Ω )
& insulation (M Ω )
Replace Fan Motor
Compressor Motor damaged ( to replace compressor)
Thermostat setting too high
Protection Device Actuated
Reset
Compressor locked (to replace compressor)
Voltage supply not within range
Check motor resistance ( Ω ) and insulation (M Ω)
Compressor
Capacitor Defective
Loose Connections,
Improper wiring
Regular but fails
to start
Irregular
PRESSURE
PROBABLE CAUSE
Circuit
To
o
Lo
w
A
L
ittl
e
Lo
w
Norma
l
A
L
ittl
e
H
ig
h
To
o
H
ig
h
High Side
Low Side
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. oil).
3. Obstructed air-intake/discharge.
4. Short circuiting of hot air at condensing unit.
High Side
Low Side
1. Poor compression/no compression (compressor defective.)
2. Check valve stick in open position.
3. Reversing valve leaking.
High Side
Low Side
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged/dirty (indoor unit).
4. Indoor fan locked (cooling).
High Side
Low Side
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
High Side
Low Side
1. Air intake temperature of indoor unit too high.
10. Troubleshooting
Содержание WinterSpa RHR-C Series
Страница 1: ...Heat Reclaim TM RHR 1214 A TECHNICAL MANUAL...
Страница 11: ...9 TM RHR 1214 A 5 Refrigerant Cycle Diagram...
Страница 14: ...12 TM RHR 1214 A 7 Wiring Diagram Indoor Unit Outdoor Unit Model RHR10CV1...
Страница 15: ...13 TM RHR 1214 A Model RHR15CV1 Indoor Unit Outdoor Unit...
Страница 16: ...14 TM RHR 1214 A Model RHR20CV1 Indoor Unit Outdoor Unit...
Страница 17: ...15 TM RHR 1214 A Model RHR25CV1 Indoor Unit Outdoor Unit...
Страница 18: ...16 TM RHR 1214 A Model RHR30BV1 Indoor Unit Outdoor Unit...
Страница 25: ...23 TM RHR 1214 A Tank Installation Diagram 9 22...