Troubleshooting by Indication on the Remote Controller
61
Remote Controller Display
A6
Applicable Models
R-22: FXM200, 250L
R-410A: FXMQ-MA
Method of Error Detection
This error is detected by detecting that the individual
power supply for the fan turns OFF.
Error Decision Conditions
When it is not detected that the individual power supply
for the indoor unit fan turns ON while in operation.
Supposed Causes
Defective power supply for the indoor unit fan motor
Clogged drain piping
Actuation of the indoor unit safety device
Defective contact in the fan wiring circuit