Troubleshooting by Indication on the Remote Controller
55
3.5
A6
Indoor Unit Fan Motor
Abnormality
Remote Controller Display
A6
Applicable Models
FXD(Q)
Method of Error Detection
This error is detected if there is no revolutions detection
signal output from the fan motor.
Error Decision Conditions
When no revolutions can be detected even at the
maximum output voltage to the fan
Supposed Causes
Defective indoor fan motor
Broken wires