SiME341909EA
Normal Control
Part 4 Functions and Control
61
5. Normal Control
5.1 List of Functions in Normal Control
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
: equipped
—: not equipped
5.2 Compressor Control
In order to provide a steady capacity, the compressor capacity is controlled to achieve
temperature Te during cooling operation.
During cooling operation
The compressor capacity is controlled so Te approaches TeS (target value of temperature).
1. VRTsmart Control
When all the connected indoor units are VRTsmart control applicable models
∗
Applicable models: FXFSQ-AR, FXDQ-PD, FXDQ-ND, FXMQ-PB, FXAQ-AR
The required capacity is calculated based on the operation condition of each individual indoor
unit and this data is transmitted to the outdoor unit. The outdoor unit adjusts the refrigerant
temperature of the whole system to an adequate value according to the indoor unit that needs
the most capacity.
In case of target evaporation temperature adjustment, first the capacity is adjusted by changing
the indoor unit airflow to L tap. If the capacity is still too much, the target evaporation
temperature is elevated further to adjust.
2. VRT Control
When one or more of the connected indoor units are not VRTsmart control applicable
models
If the required capacity becomes low in all indoor units (Room temperature Th1 – set
temperature), the target evaporation temperature is elevated further to adjust. In the outdoor
unit, the difference of temperature (∆T) in all indoor units is checked and the set temperature is
changed. Unlike VRTsmart control, there is no airflow control of the indoor units.
3. Te fix Control
The target evaporation temperature is not changed.
Te value (Set in mode 2-8)
Te: Low pressure equivalent saturation temperature (°C)
TeS: Te target value (varies according to Te setting, compressor operation frequency, etc.)
Part Name
Electric
Symbol
RXQ6/8AR
RXQ10/12AR
RXQ14/16AR
Function of Functional Part
Compressor 1
M1C
PI control by Te target.
Compressor 2
M2C
—
—
Inverter fan 1
M1F
Fan speed 10 steps to keep
minimum Tc target 34°C.
Inverter fan 2
M2F
—
Electronic expansion valve
(Injection)
Y2E
0-480 pulse at compressor on
Electronic expansion valve
(Refrigerant auto charge)
Y4E
Minimum pulse
Solenoid valve (Oil return 1)
Y3S
Only close if Pc – Pe < 0.3 MPa
(when compressor off)
Solenoid valve (Oil return 2)
Y4S
—
—
Standard (Factory
setting)
High
6
7
8
9
10
11
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...