Troubleshooting by Error Code
Part 6 Service Diagnosis
255
5.60 Transmission Error between Centralized Controller and
Indoor Unit
Applicable
Models
All indoor unit models
Schedule timer
Central remote controller
Error Code
UE
Method of Error
Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Error Decision
Conditions
Transmission is not carried out normally for a certain amount of time
Supposed
Causes
Transmission error between optional controllers for centralized controller and indoor unit
Connector for setting main controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Defective PCB for central remote controller
Defective indoor unit PCB
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...