SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
203
Reference
5.29 Electronic Expansion Valve Coil Abnormality
Applicable
Models
All outdoor unit models
Error Code
E9
Method of Error
Detection
Detect according to whether or not there is continuity across the electronic expansion valve
coils (Y2E, Y4E).
Error Decision
Conditions
When no current flows through common (COM+) at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connectors from electronic expansion valves (Y2E, Y4E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB
Troubleshooting
CHECK 18
Refer to page 278.
Turn OFF the power supply
once, and then turn it ON again.
Return to normal?
Investigate external causes other than
failures (e.g. noise).
Replace the outdoor unit main PCB
(A1P).
YES
NO
Connector for
the electronic expansion
valve of the outdoor unit main
PCB (A1P) is
connected.
CHECK 18
The resistance of
the electronic expansion
valve coil is
normal.
Properly and securely connect the
connector.
NO
YES
Is sub code one
of the following?
E9-48,49,50,51,
52,53,54,55,56
Replace the defective electronic
expansion valve coil.
YES
NO
NO
YES
CHECK 18
The resistance of the
electronic expansion
valve coil is
normal.
Replace the electronic expansion
valve coil.
NO
Replace the outdoor unit main PCB
(A1P).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check for electronic expansion valves applicable to the error code
E9
while
in monitor mode.
• Sub code
Y2E: E9-03 (Master), E9-06 (Slave 1), E9-09 (Slave 2)
Y4E: E9-26 (Master), E9-27 (Slave 1), E9-28 (Slave 2)
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...