Check
SiME341909EA
278
Part 6 Service Diagnosis
6.13 Electronic Expansion Valve Coil Check
CHECK 18
Remove the connector for electronic expansion valve from PCB. Measure the resistance value
between pins and check the continuity to judge the condition.
The normal products will show the following conditions.
Outdoor unit
RXQ6/8AR
RXQ10-16AR
White (1)
Yellow (2)
Orange (3)
Blue (4)
— (5)
Red (6)
X22A (Y2E)
Orange (1)
Red (2)
Yellow (3)
Black (4)
— (5)
COM+Gray (6)
X25A (Y4E)
Measuring points
Judgment criteria
1-6
35-55
Ω
2-6
3-6
4-6
Orange (1)
Red (2)
Yellow (3)
Black (4)
— (5)
COM+Gray (6)
X22A (Y2E)
X25A (Y4E)
Measuring points
Judgment criteria
1-6
35-55
Ω
2-6
3-6
4-6
Содержание VRV X RXQ10ARYFK
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...