10T8Y1B
VRV-W IV System Air Conditioner
4P399208-1 – 2015.01
Installation and operation manual
23
Point of attention regarding quality of the public electric power
supply
This equipment complies with respectively:
EN/IEC 61000-3-11
(1)
provided that the system impedance Z
sys
is less than or equal to Z
max
.
EN/IEC 61000-3-12
(2)
provided that the short-circuit power S
sc
is greater than or equal to the minimum S
sc
value.
At the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
respectively:
Z
sys
less than or equal to Z
max
.
S
sc
greater than or equal to the minimum S
sc
value.
14.2. Internal wiring – Parts table
Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
A1P........................ Printed circuit board (main)
A2P........................ Printed circuit board (inv)
A3P........................ Printed circuit board (noise filter)
A4P........................ Printed circuit board (fan)
BS1~BS5............... Push button switch (A1P)
C63,C66 ................ Capacitor (A3P, A6P)
DS1........................ DIP switch (A1P)
E1HC ..................... Crankcase heater
F1U........................ Fuse (250 V, 5 A, T) (A3P)
F1U,F2U ................ Fuse (250 V, 10 A, T) (A1P)
H1P~8P ................. Pilot lamp (A1P) (service monitor - orange)
[H2P] - prepare, test ... flickering
- malfunction detection ... light up
HAP ....................... Pilot lamp (A1P) (service monitor - green)
K1M ....................... Magnetic contactor (M1C) (A2P)
K1R........................ Magnetic relay (A2P)
K3R........................ Magnetic relay (Y2S) (A1P)
K5R........................ Magnetic relay (Y3S) (A1P)
K6R........................ Magnetic relay (Y4S) (A1P)
K7R........................ Magnetic relay (M1F, M2F) (A1P)
K8R........................ Magnetic relay (Y6S) (A1P)
K9R........................ Magnetic relay (Y2S) (A1P)
K10R...................... Magnetic relay (operation output) (A1P)
K11R ...................... Magnetic relay (Y5S) (A1P)
K12R...................... Magnetic relay (Y7S) (A1P)
K13R...................... Magnetic relay (E1HC) (A1P)
L1R ........................ Reactor
M1C ....................... Motor (compressor)
M1F,M2F................ Motor (fan inverter cooling)
PS.......................... Switching power supply
Q1RP..................... Phase reversal detection circuit (A1P)
R50, R59 ............... Resistor
R95 ........................ Resistor (current limiting)
R1T........................ Thermistor (fin) (A2P)
R2T........................ Thermistor (suction)
R3T........................ Thermistor (M1C, discharge)
R4T........................ Thermistor (heat exc. gas pipe)
R5T........................ Thermistor (subcool heat exc.)
R6T........................ Thermistor (receiver liquid pipe)
S1NPH................... Pressure sensor (high)
S1NPL ................... Pressure sensor (low)
S1PH ..................... Pressure switch (high)
S1S........................ Selector switch
S2S........................ Selector switch
T1A ........................ Current sensor (A4P)
T1R........................ Transformer
V1CP ..................... Safety devices input
V1R........................ Diode bridge (A2P)
V2R........................ Power module (A2P)
X1A, X3A ............... Connector (Y1E, Y3E)
X1M ....................... Terminal strip (power supply)
X1M ....................... Terminal strip (control) (A1P)
X2M ....................... Terminal strip (operation output)
X3M ....................... Terminal strip (interlock)
X4M ....................... Terminal strip (M1C)
Y1E........................ Electronic expansion valve (main)
Y3E........................ Electronic expansion valve (subcool)
Y1S........................ Solenoid valve (hot gas bypass)
Y2S........................ Solenoid valve (oil return)
Y3S........................ Solenoid valve (receiver pressurization)
Y4S........................ Solenoid valve (receiver gas purge)
Y5S........................ Solenoid valve (main 4-way valve)
Y6S........................ Solenoid valve (liquid pipe)
Y7S........................ Solenoid valve (sub 4-way valve)
Z1C........................ Noise filter (ferrite core)
Z1F ........................ Noise filter (with surge absorber)
L1,L2,L3................. Live
N ............................ Neutral
............... Field wiring
................. Terminal strip
......................... Connector
......................... Terminal
.......................... Protective earth (screw)
WARNING
The reversed phase protection detector of this
product only functions when the product starts up.
Consequently reversed phase detection is not
performed during normal operation of the product.
The reversed phase protection detector is designed to
stop the product in the event of an abnormality when
the product is started up.
Replace two of the three phases (L1, L2, and L3)
during reverse-phase protection abnormality.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off
while the product is operating, attach a reversed
phase protection circuit locally. Running the product in
reversed phase can break the compressor and other
parts.
(1)
European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current
≤
75 A.
(2)
European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and
≤
75 A per phase.
Z
max
(
Ω
)
Minimum S
sc
value (kVA)
RWEYQ8
—
—
RWEYQ10
—
—
RWEYQ16
—
1811
RWEYQ18
—
1811
RWEYQ20
—
1811
RWEYQ24
—
2716
RWEYQ26
—
2716
RWEYQ28
—
2716
RWEYQ30
—
2716
INFORMATION
Multi outdoor unit systems are standard combinations.