Point of attention regarding quality of the public electric power 
supply

This equipment complies with respectively:

EN/IEC 61000-3-11

(1) 

provided that the system impedance Z

sys

 

is less than or equal to Z

max

.

EN/IEC 61000-3-12

(2)

 provided that the short-circuit power S

sc

 

is greater than or equal to the minimum S

sc

 value.

At the interface point between the user's supply and the public 
system. It is the responsibility of the installer or user of the equipment 
to ensure, by consultation with the distribution network operator if 
necessary, that the equipment is connected only to a supply with 
respectively:

Z

sys

 less than or equal to Z

max

.

S

sc

 greater than or equal to the minimum S

sc

 value.

14.2. Internal wiring – Parts table

Refer to the wiring diagram sticker on the unit. The abbreviations 
used are listed below:
A1P........................ Printed circuit board (main)
A2P........................ Printed circuit board (inv)
A3P........................ Printed circuit board (noise filter)
A4P........................ Printed circuit board (fan)
BS1~BS5............... Push button switch (A1P)
C63,C66 ................ Capacitor (A3P, A6P)
DS1........................ DIP switch (A1P)
E1HC ..................... Crankcase heater
F1U........................ Fuse (250 V,  5 A, T) (A3P)
F1U,F2U ................ Fuse (250 V,  10 A, T) (A1P)

H1P~8P ................. Pilot lamp (A1P) (service monitor - orange)

 

[H2P] - prepare, test ... flickering

 

          - malfunction detection ... light up

HAP ....................... Pilot lamp (A1P) (service monitor - green)
K1M ....................... Magnetic contactor (M1C) (A2P)
K1R........................ Magnetic relay (A2P)
K3R........................ Magnetic relay (Y2S) (A1P)
K5R........................ Magnetic relay (Y3S) (A1P)
K6R........................ Magnetic relay (Y4S) (A1P)
K7R........................ Magnetic relay (M1F, M2F) (A1P)
K8R........................ Magnetic relay (Y6S) (A1P)
K9R........................ Magnetic relay (Y2S) (A1P)
K10R...................... Magnetic relay (operation output) (A1P)
K11R ...................... Magnetic relay (Y5S) (A1P)
K12R...................... Magnetic relay (Y7S) (A1P)
K13R...................... Magnetic relay (E1HC) (A1P)
L1R ........................ Reactor
M1C ....................... Motor (compressor)
M1F,M2F................ Motor (fan inverter cooling)
PS.......................... Switching power supply
Q1RP..................... Phase reversal detection circuit (A1P)
R50, R59 ............... Resistor
R95 ........................ Resistor (current limiting)
R1T........................ Thermistor (fin) (A2P)
R2T........................ Thermistor (suction)
R3T........................ Thermistor (M1C, discharge)
R4T........................ Thermistor (heat exc. gas pipe)
R5T........................ Thermistor (subcool heat exc.)
R6T........................ Thermistor (receiver liquid pipe)
S1NPH................... Pressure sensor (high)
S1NPL ................... Pressure sensor (low)
S1PH ..................... Pressure switch (high)
S1S........................ Selector switch
S2S........................ Selector switch
T1A ........................ Current sensor (A4P)
T1R........................ Transformer
V1CP ..................... Safety devices input
V1R........................ Diode bridge (A2P)
V2R........................ Power module (A2P)
X1A, X3A ............... Connector (Y1E, Y3E)
X1M ....................... Terminal strip (power supply)
X1M ....................... Terminal strip (control) (A1P)
X2M ....................... Terminal strip (operation output)
X3M ....................... Terminal strip (interlock)
X4M ....................... Terminal strip (M1C)
Y1E........................ Electronic expansion valve (main)
Y3E........................ Electronic expansion valve (subcool)
Y1S........................ Solenoid valve (hot gas bypass)
Y2S........................ Solenoid valve (oil return)
Y3S........................ Solenoid valve (receiver pressurization)
Y4S........................ Solenoid valve (receiver gas purge)
Y5S........................ Solenoid valve (main 4-way valve)
Y6S........................ Solenoid valve (liquid pipe)
Y7S........................ Solenoid valve (sub 4-way valve)
Z1C........................ Noise filter (ferrite core)
Z1F ........................ Noise filter (with surge absorber)
L1,L2,L3................. Live
N ............................ Neutral

............... Field wiring

................. Terminal strip

......................... Connector
......................... Terminal

.......................... Protective earth (screw)

WARNING

The reversed phase protection detector of this 
product only functions when the product starts up. 
Consequently reversed phase detection is not 
performed during normal operation of the product.

The reversed phase protection detector is designed to 
stop the product in the event of an abnormality when 
the product is started up.

Replace two of the three phases (L1, L2, and L3) 
during reverse-phase protection abnormality.

If there exists the possibility of reversed phase after a 
momentary black out and the power goes on and off 
while the product is operating, attach a reversed 
phase protection circuit locally. Running the product in 
reversed phase can break the compressor and other 
parts.

(1)

European/International Technical Standard setting the limits for voltage 
changes, voltage fluctuations and flicker in public low-voltage supply 
systems for equipment with rated current 

75 A.

(2)

European/International Technical Standard setting the limits for harmonic 
currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

Z

max

(

Ω

)

Minimum S

sc

 

value (kVA)

RWEYQ8

RWEYQ10

RWEYQ16

1811

RWEYQ18

1811

RWEYQ20

1811

RWEYQ24

2716

RWEYQ26

2716

RWEYQ28

2716

RWEYQ30

2716

INFORMATION

Multi outdoor unit systems are standard combinations.

Содержание VRV-WIV RWEYQ-T Series

Страница 1: ...INSTALLATION AND OPERATION MANUAL RWEYQ8T8Y1B RWEYQ10T8Y1B System Air Conditioner...

Страница 2: ...1 2 3 1 10 19 3 4 15 18 16 9 2 5 21 20 11 13 12 6 7 18 8 14 SV SV INV HPS SV SV SV 1 2 5 6 7 8 9 10 11 12 13 15 16 18 17 21 19 20 18 3 4 18 17 1 2 3...

Страница 3: ...sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Ri...

Страница 4: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimal...

Страница 5: ...tons on the logic board 28 15 2 Operating the push buttons and DIP switches on the logic board 29 16 Charging refrigerant 31 16 1 Precautions 31 16 2 Important information regarding the refrigerant us...

Страница 6: ...nger of burning and scalding DANGER ELECTRICAL SHOCK Switch off all power supply before removing the electrical component box service panel or before making any connections or touching electrical part...

Страница 7: ...cks or fire A high surge current from lightning or other sources may cause damage to the air conditioner Be sure to install an earth leakage breaker Failure to install an earth leakage breaker may res...

Страница 8: ...eating cooling or simultaneous heating cooling is possible 1 Closed cooling tower 2 Boiler 3 VRV IV water cooled unit 4 VRV DX indoor unit 5 User interface Dedicated depending on indoor unit type 6 BS...

Страница 9: ...water cooled units This manual has been prepared to ensure adequate maintenance of the unit and it will provide help in case problems occur 4 Accessories Make sure that the following accessories are...

Страница 10: ...it Main components see figure 1 figure 2 and figure 3 1 Compressor INV 2 Plate heat exchanger 3 Receiver 4 Oil separator 5 Electronic expansion valve main Y1E 6 Electronic expansion valve sub cool Y3E...

Страница 11: ...exceed the allowable piping length See 9 Refrigerant pipe size and allowable pipe length on page 10 Be sure that sufficient precautions are taken in accordance with the applicable legislation in case...

Страница 12: ...ay exceed the allowable limit depending on room size Due to this it could be necessary to take measures against leakage Refer to 19 Caution for refrigerant leaks on page 42 7 Dimensions and service sp...

Страница 13: ...sure to use the standard supplied accessories and dedicated parts as installation parts 1 Patch plates or clothes 2 Belt sling 8 3 Unpacking Remove the packaging material from the unit Take care not...

Страница 14: ...revented from getting mixed into the system Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce earth s protection against harmful ultraviolet radiation R410...

Страница 15: ...joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the capacity of the outdoor unit e g Refnet joint a For Refnet joints other than the f...

Страница 16: ...units Equivalent piping length 2 pipe length between outdoor 1 and indoor units Total piping length total piping length from the outdoor 1 to all indoor units Difference in height between outdoor and...

Страница 17: ...1 B6 Indoor units 1 8 Heat recovery system 1 6 Cooling only 7 8 H1 H2 Unit 1 REFNET joint A G BS units B1 B4 Indoor units 1 8 Heat recovery system 1 6 Cooling only 7 8 a b c d e 1 2 3 4 5 6 7 8 First...

Страница 18: ...c d e f g p a h 40 m 9 7 Multi outdoor unit system piping installation 9 7 1 Precautions when connecting piping between outdoor units To connect the piping between outdoor units an optional multi outd...

Страница 19: ...n Do not use anti oxidants when brazing the pipe joints Residue can clog pipes and break equipment Do not use flux when brazing copper to copper refrigerant piping Use phosphor copper brazing filler a...

Страница 20: ...refer to the installation manual delivered with the kit 1 Horizontal surface 1 Mount the Refnet joint so that it branches either horizontally or vertically 2 Mount the Refnet header so that it branche...

Страница 21: ...lly open the 19 1 or 25 4 gas line stop valve turn the hexagonal wrench until a torque between 27 and 33 N m is achieved Inadequate torque may cause leakage of refrigerant and breakage of the stop val...

Страница 22: ...eck for any leakages in the refrigerant piping Perform vacuum drying to remove all moisture air or nitrogen in the refrigerant piping If there is a possibility of moisture being present in the refrige...

Страница 23: ...ion of the pipe Take preventive measures as necessary for example by insulating the connection on the water pipe The connection port for water piping is located in the front The connection ports for d...

Страница 24: ...iping between this gate valve and the outdoor unit for cleaning by chemicals For the purpose of cleaning and water draining from the outdoor unit water draining during a long period of non use in wint...

Страница 25: ...freezing protection device was activated When the freezing protection device was activated during operation eliminate the cause before restarting operation If the freezing protection device was activ...

Страница 26: ...ch agent has no corrosive features against stainless steel and copper For details of the cleaning method ask the manufacturer of the related cleaning agent After cleaning has been completed check that...

Страница 27: ...at exc R6T Thermistor receiver liquid pipe S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH Pressure switch high S1S Selector switch S2S Selector switch T1A Current sensor A4P T1R Transformer...

Страница 28: ...1 2 3 3 4 4 5 6 9 7 A B 3 4 6 7 5 8 1 2 3 4 9 CAUTION Do not apply excessive force when opening the electrical component box cover Excessive force can deform the cover Minimum circuit ampere Recommend...

Страница 29: ...Branch line 1 5 Branch line 2 6 Branch line 3 7 No branch is allowed after branch 8 Central user interface etc A Transmission wiring between outdoor unit and indoor unit s B Transmission wiring betwee...

Страница 30: ...ndoor units is connected is master unit 14 6 3 Power supply wiring and transmission wiring in the unit Make sure to connect the power wire to the power terminal block and fix it using attached clamp a...

Страница 31: ...ly wiring NOTICE When routing earth wires secure clearance of 50 mm or more away from compressor lead wires Failure to observe this instruction properly may adversely affect correct operation of other...

Страница 32: ...master unit only 1 Outdoor unit A 2 Outdoor unit B 3 Outdoor unit C 4 Adapter for external control 5 Interlock circuit of water pump 6 Outdoor outdoor transmission wiring 7 Use the conductor of sheat...

Страница 33: ...nged or when an additional indoor unit is installed When above situation cannot be confirmed after 12 minutes the malfunction code can be checked on the indoor unit user interface and the outdoor unit...

Страница 34: ...5 seconds you can select the desired setting It is done by pushing BS2 Accessing the selected setting s value is done by pushing BS3 one time Now BS2 is used to select the required value of the select...

Страница 35: ...T selector refer to the manual of the cool heat selector switch OFF not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to do with DIP switch DS2 DS3 1 4 NOT USED DO NOT...

Страница 36: ...ition Charge the liquid refrigerant with the cylinder in upside down position NOTICE Charging with an unsuitable substance may cause explosions and accidents so always make sure that the appropriate r...

Страница 37: ...LP gas Leave the suction gas valve closed in case of heat pump system 10 Damaged equipment Check the inside of the unit for damaged components or squeezed pipes 11 Refrigerant leak Check the inside o...

Страница 38: ...n wiring path between outdoor and outdoor units Q1 Q2 communication line M 14 shows the latest malfunction code M 15 shows the 2nd last malfunction code M 16 shows the 3rd last malfunction code When t...

Страница 39: ...ant recovery vacuuming mode Value 2 9 Tc target C 1 41 3 43 6 46 H1P H2P H3P H4P H5P H6P H7P ON w x x x x c x OFF w x x x x x c H1P H2P H3P H4P H5P H6P H7P ON w x x x x c x OFF w x x x x x c H1P H2P H...

Страница 40: ...saving and optimum operation on page 37 Value 2 32 Restriction reference 1 Function not active default 2 Follows 2 30 setting 4 Follows 2 31 setting Value 2 49 Te target C 2 6 3 7 4 8 5 9 default 6 10...

Страница 41: ...city is not the same as under basic operation For details concerning Hi sensible applications please contact your dealer To activate this setting under cooling operation change field setting 2 8 to th...

Страница 42: ...becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the powerful and quick comfor...

Страница 43: ...on A Set room temperature B Operation start C Operation time D Mild E Quick F Powerful Example Automatic mode during heating A Default automatic mode peak capacity B Load curve C Initial Tc value in a...

Страница 44: ...y be necessary to provide a logbook with the equipment containing at least info on maintenance repair work results of tests stand by periods CAUTION Do not perform the test operation while working on...

Страница 45: ...nd confirm that the abnormality is properly corrected 18 2 Malfunction code list In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After cor...

Страница 46: ...a humanly space is limited to 0 35 kg m3 for R407C and 0 44 kg m3 for R410A 1 Direction of the refrigerant flow 2 Room where refrigerant leak has occurred outflow of all the refrigerant from the syste...

Страница 47: ...sure the voltage between terminals on the terminal block for power supply with a tester and confirm that the power supply is shut off In addition measure points as shown in the figure below with a tes...

Страница 48: ...relative value depending on the distance and acoustic environment For more details refer to sound level drawings in the technical data book RWEYQ8 RWEYQ10 Power supply name Y1 phase 3N frequency Hz 5...

Страница 49: ...optionally be combined to the products as per the subject of this manual Field supply Equipment which needs to be installed according to instructions in this manual but which are not supplied by Daik...

Страница 50: ...a water leakage electric shock and fire Do not place a flammable spray bottle near the air conditioner and do not use sprays Doing so may result in a fire Before cleaning be sure to stop the operatio...

Страница 51: ...object The user interface may be damaged Never pull or twist the electric wire of the user interface It may cause the unit to malfunction Never inspect or service the unit by yourself Ask a qualified...

Страница 52: ...angeover remote control switch Operating the changeover remote control switch 1 Select operation mode with the cool heat changeover switch as follows Cooling operation Heating operation Fan only opera...

Страница 53: ...ro computer controls the air flow direction which may be different from the display The air flow direction can be adjusted in one of the following ways The air flow flap itself adjusts its position Th...

Страница 54: ...or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Ventilate often Extended use requires special attention to ventilation Keep doors and windo...

Страница 55: ...t half a day in order to dry the interior of the units Refer to 6 1 Cooling heating fan only and automatic operation on page 48 for details on fan only operation Turn off the power The user interface...

Страница 56: ...w change Symptom 8 3 Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency Symptom 9 Dust comes out of the unit When the unit is used for the first time...

Страница 57: ...me of the air conditioner The manufacturing number stated on the nameplate of the unit The installation date The symptoms or malfunction and details of the defect 11 2 2 Recommended inspection and mai...

Страница 58: ...AJ Capacity setting malfunction indoor C1 Transmission malfunction between main PCB and sub PCB indoor C4 Heat exchanger thermistor malfunction indoor liquid C5 Heat exchanger thermistor malfunction i...

Страница 59: ...he refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 2087 5 1 GWP global warming potential Periodical inspect...

Страница 60: ...4P399208 1 2015 01 Copyright 2015 Daikin 4P399208 1 0000000T...

Отзывы: