Troubleshooting by Error Code
Part 6 Service Diagnosis
333
5.74 Central Control Indicator Lamp Blinking (One blink)
Applicable
Models
ON/OFF controller
Centralized controller
Schedule timer
Error Code
–
Method of Error
Detection
DIII-NET communication data is used to detect the error.
Error Decision
Conditions
The previously connected centralized controller is not responding.
Control range duplication
There are multiple main centralized controllers.
There are other centralized controllers but the schedule timer is set for individual use.
There is a remote control adapter.
Supposed
Causes
Centralized controller address duplication
Poor centralized controller combination
Multiple main centralized controllers
Transmission defect between centralized controllers
Defective centralized controller PCB
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...