Troubleshooting by Error Code
SiAF332111E
314
Part 6 Service Diagnosis
Reference
5.61 Transmission Error between Remote Controller and
Indoor Unit
Applicable
Models
All indoor unit models
Error code
U5
Method of Error
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time.
Supposed
Causes
Transmission error between indoor unit and remote controller
Connection of 2 main remote controllers (when using 2 remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Transmission error caused by noise
Troubleshooting
Refer to page 43 for Main/Sub setting.
Control by 2
remote controllers
Main/Sub
setting of both
remote controllers is
set to Main.
All indoor unit
PCB microcomputer
normal monitors
blinking
Resets
normally when
power supply is turned
OFF temporarily.
NO
NO
NO
YES
NO
Replace the indoor unit
PCB.
Set one of the remote
controllers to Sub, turn OFF
the power supply temporarily,
then restart operation.
The error could be produced by
noise. Check the surrounding
area and restart operation.
The error could be produced by
noise. Check the surrounding
area and restart operation. (Ex.:
Heavy-duty wireless equipment,
etc.)
Normal.
Normal.
NO
NO
YES
YES
YES
Replace the remote controller
and restart operation.
YES
Replace the indoor unit PCB
and restart operation.
Is operation normal?
Is operation normal?
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...