SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
255
Reference
5.33 Refrigerant Overcharged
Applicable
Models
All outdoor unit models
Error Code
F6
Method of Error
Detection
Detect overcharged refrigerant according to the following thermistor temperatures during test
operation.
4/5 HP models
Outdoor air thermistor (R1T)
Heat exchanger deicer thermistor (R4T)
6/8 HP models
Outdoor air thermistor (R1T)
Heat exchanger liquid pipe thermistor (R4T)
Subcooling heat exchanger liquid pipe thermistor (R5T)
10/12 HP models
Outdoor air thermistor (R1T)
Heat exchanger liquid pipe thermistor (R4T)
Heat exchanger deicer thermistor (R7T)
Error Decision
Conditions
When the amount of refrigerant, which is calculated using the thermistor temperatures during
test operation, exceeds the regular charge amount by 30% or more.
(However, even if refrigerant is charged slightly over the regular charge amount,
F6
may be
displayed on the remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of any of the above thermistors
Abnormalities in any of the above thermistors
Troubleshooting
CHECK 11
Refer to page 350.
Check for the conditions of
mounting of the thermistors to
the piping.
Disconnect the thermistors
from the outdoor unit main
PCB, and then make
measurement of resistance
using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the thermistors
properly mounted?
CHECK 11
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...