Test Operation (4/5/10/12 HP Models)
Part 5 Field Settings and Test Operation
161
5. Test Operation (4/5/10/12 HP Models)
Follow the following procedure to conduct the initial test operation after installation.
5.1 Check Work Prior to Turning Power Supply ON
5.2 Turn Power ON
• Is the power supply appropriate?
• Have you finished a ductwork to drain?
• Have you detach transport fitting?
• Is the wiring performed as specified?
• Are the designated wires used?
• Is the grounding work completed?
Use a 500 V Megger tester to measure the insulation.
Do not use a Megger tester for low voltage circuits.
• Are the setscrews of wiring not loose?
• Is the electrical component box covered with an insulation
cover completely?
• Is pipe size proper? (The design pressure of this product is
4.0 MPa.)
• Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated.
(Otherwise causes water leak.)
• Are respective stop valves on liquid and gas line securely
open?
• Is refrigerant charged up to the specified amount?
If insufficient, charge the refrigerant from the service port of
stop valve on the liquid side while the outdoor unit is not
operating after turning power ON.
• Has the amount of refrigerant charge been recorded on
“Record Chart of Additional Refrigerant Charge Amount”?
Check on refrigerant piping /
insulation material
Check on amount of refrigerant
charge
Check the below items.
•
Power wiring
•
Control transmission wiring
between units
•
Earth wire
• Be sure to turn the power ON 6 hours before starting
operation to protect compressors.
• Close outside panels of the outdoor unit.
Turn outdoor unit power ON.
Turn indoor unit power ON.
Carry out field setting on
outdoor PCB
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...