Field Settings for Outdoor Unit (6/8 HP Models)
SiAF332111E
144
Part 5 Field Settings and Test Operation
3.8 Night-Time Low Noise Operation and Demand Operation
Night-time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adaptor (optional), you can lower operating noise by 2-3 dB.
A. When night-time low noise operation is carried out by external contact (with the use of
the external control adaptor for outdoor unit)
1. Connect external control adaptor for outdoor unit and short circuit terminal of night-time low
noise operation (Refer below figure). If carrying out demand or low noise input, connect the
adaptor’s terminals as shown below. External control adaptor for outdoor unit Host computer
Outside wiring indicated monitor panel by dotted line or demand controller
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select an external low noise level for the item 2-25.
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If
the condition is set to ON, when the air conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When night-time low noise operation is carried out automatically (External control
adaptor for outdoor unit is not required)
1. While in setting mode 2, select a night-time low noise operation level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 06:00 AM, 07:00 AM, or 08:00 AM) for the item 2-27. (Use the ending time as a guide since
it is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the system will be put
into normal operation mode even during night-time.)
Setting
Content
Level 1
Set the outdoor fan to Step 8 or lower.
Level 2
Set the outdoor fan to Step 7Y or lower.
Level 3
Set the outdoor fan to Step 6 or lower.
O
u
tside
w
iring indicated
b
y dotted line
External control
adaptor for
o
u
tdoor
u
nit
Host comp
u
ter
monitor panel
or demand
controller
X
X
X
X
F1
F2
P3
P4
F1
F2
P3
P4
X
X
X
X
X
X
1
2
3
C
Demand
Lo
w
noise
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...