Troubleshooting by Error Code
SiUS342004EB
289
Part 6 Service Diagnosis
3.37 Compressor Damage Alarm
Applicable
Models
All outdoor unit models
Error Code
E6
Method of Error
Detection
Determine the symptom to be error by detecting the revolutions of the compressor and pressure
values detected by the high and low pressure sensors, and further making a comparison between a
theoretical current value of the compressor calculated from parameters detected and an actual
current value detected by the power transistor.
Error Decision
Conditions
When a state in which the actual current value of the compressor is abnormally high (by 130% or
more) compared to the theoretical current value continues for a period of 30 minutes.
In case of a system with multi outdoor units, the system will return an alarm if there is any
operational unit other than that applicable to
E6
or determine to be error if not.
Supposed
Causes
Defective compressor
Defective high pressure sensor
Defective low pressure sensor
Defective outdoor unit main PCB
Defective inverter PCB
Troubleshooting
NO
YES
Are the
characteristics of
the high pressure
sensor normal?
(
∗
1)
(1) Mount a pressure gauge on the high and low pressure
service ports.
(2) Reset the power supply, and then restart the operation.
Replace the high pressure sensor
(S1NPH).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Are the
characteristics of
the low pressure
sensor normal?
(
∗
1)
Replace the low pressure sensor
(S1NPL).
Connect the service checker to compare the high
pressure and low pressure checked by the service
checker and the actual measured values of the high and
low pressure sensors. (
∗
1)
Service Checker
A
CHECK 12
Go to the next page.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...