SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
188
Note(s)
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set
temperature) is less than 1.5°C (2.7°F).
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set
temperature) is 3°C (5.4°F) or more.
[2-32]:
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value: 0 (OFF).
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Change [2-32]: 0,1 or 2 in function of required limitation.
[2-34]:
Indoor fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air
temperature for energy saving
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units capacity
130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity
130%.
2
Fan speed follows the setting of remote controllers (not limited by indoor units
connection capacity).
3
Limited in cooling when Ta < 29.5°C (85.1°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 32.5°C (90.5°F) or Indoor condition is in condition B (
2)
4
Limited in cooling when Ta < 23.5°C (74.3°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 26.5°C (79.7°F) or Indoor condition is in condition B (
2)
5
Limited in cooling when Ta < 19.3°C (66.7°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 22.3°C (72.1°F) or Indoor condition is in condition B (
2)
6
Limited in cooling when Ta < 29.5°C (85.1°F)
Returned when Ta > 32.5°C (90.5°F)
7
Limited in cooling when Ta < 23.5°C (74.3°F)
Returned when Ta > 26.5°C (79.7°F)
8
Limited in cooling when Ta < 19.3°C (66.7°F)
Returned when Ta > 22.3°C (72.1°F)
[2-35]:
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (130 ft), the setting [2-35]
should be changed to 0.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...