Field Settings for Outdoor Unit
SiUS342004EB
175
Part 5 Field Settings and Test Operation
2.5 Monitoring Function and Field Settings
The operation of the outdoor unit can further be defined by changing some field settings. Next to
making field settings it is also possible to confirm the current operation parameters of the unit. The
setting can also be performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained
in detail.
Making settings is done via the master outdoor unit.
2.5.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents
can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you are checking is a master, slave 1 or slave 2 unit.
No indication: undefined situation
0: outdoor unit is master unit
1: outdoor unit is slave 1 unit
2: outdoor unit is slave 2 unit
Master, slave 1 and slave 2 indications are relevant in multiple outdoor unit system
configurations. The allocation of which outdoor unit is master, slave 1 or slave 2 are
decided by the unit’s logic.
The master unit must be used to input field settings in mode 2.
[1-1]:
shows the status of night-time low noise operation.
0: unit is currently not operating under low noise restrictions
1: unit is currently operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate
night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by field
setting. The unit will operate at the selected low noise level during the selected time
frames.
The second method is to enable night-time low noise operation based on an external
input. For this operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation.
0: unit is currently not operating under power consumption limitations
1: unit is currently operating under power consumption limitation
Power consumption limitation reduces the power consumption of the unit compared
to nominal operating conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit
system.
The first method is to enable a forced power consumption limitation by field setting.
The unit will always operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external
input. For this operation an optional accessory is required.
[1-5]:
shows the current Te target parameter position.
[1-6]:
shows the current Tc target parameter position.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...