SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
152
Note(s)
Note(s)
1.3.10 Detection Rate Setting (For units with an infrared presence sensor
only)
Set the sensitivity of the infrared presence sensor.
The infrared presence sensor can be disabled by selecting the Second code No.
04
.
When the infrared presence sensor is disabled, the remote controller menu does not display some
functions such as the automatic draft reduction, energy-saving operation in absence and halt in
absence.
: Factory setting
1.3.11 Automatic Airflow Adjustment
Make external static pressure setting automatically using automatic airflow adjustment (11 (21)-7),
or manually using external static pressure settings (13 (23)-6).
The volume of blow-off air is automatically adjusted to the rated quantity.
Make settings before performing the test operation of the outdoor unit.
Setting procedure
1. Make sure that electric wiring and duct construction have been completed. In particular, if the
closing damper is installed on the way of the duct, make sure that it is open. In addition, make
sure that a field-supplied air filter is installed within the air passageway on the suction port side.
2. If there are multiple blow-off and suction ports, adjust the throttle part so that the airflow volume
ratio of each suction/blow-off port conforms to the designed airflow volume ratio. In that case,
operate the unit with fan operation mode. When you want to change the airflow rate, adjust it by
pressing the airflow rate control button to select High, Middle or Low.
3. Make settings to adjust the airflow rate automatically. After setting to fan operation mode, enter
the field setting mode while operation is stopped and then select the Mode No. 11 (21), set the
First Code No. to
7
and the Second Code No. to
03
.
4. After setting, return to the basic screen (to the normal mode in the case of a wireless remote
controller) and press the ON/OFF button. Fan operation for automatic airflow adjustment will
start with the operation lamp turned ON. Do not adjust the throttle part of the suction and
blow-off ports during automatic adjustment. After operation for approximately one to fifteen
minutes, airflow adjustment automatically stops with the operation lamp turned OFF.
5. After operation stopped, make sure that the Second Code No. is set to
02
as in the following
table by indoor unit with the Mode No. 11 (21). If operation does not stop automatically or the
Second Code No. is not set to
02
, return to the step 3 above to make settings again.
: Factory setting
1. Make sure that the external static pressure is within the range of specifications before making
settings. If it is outside the range, automatic adjustment fails, which may cause an insufficient
airflow volume or leakage of water.
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
make sure to perform automatic airflow adjustment again.
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
6
01
High sensitivity
02
Low sensitivity
03
Standard sensitivity
04
Infrared presence sensor disabled
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
7
01
OFF
02
Completion of airflow adjustment
03
Start of airflow adjustment
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...