SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
150
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis
required for reliability.
1 The second code No. 07 is used for disabling the starting of gas furnace interlocking with room
temperature.
1.3.7 Setting of Airflow Rate when Heating
The fan revolution is changed to maintain the sufficient distance for warm air to reach during the
heating operation. The setting should be changed depending on the installation condition of the
unit.
: Factory setting
Note that this setting is effective only during the heating operation.
Second Code No.
Ton
01
02
03
04
05
06
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
To
ff
06
0.5°C (0.9°F)
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
03
–1°C (–1.8°F)
h
h
h
—
—
—
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
—
: Available
: Not available
CXTQ-TA
: Factory setting
Mode
No.
First Code
No.
Symbol
Second Code No.
01
02
03
04
05
06
07 (
1)
11 (21)
1
Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
2
Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
–98°C
(–144.4°F)
Second Code No.
Ton
01
02
03
04
05
06
07
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
To
ff
07
–98°C (–144.4°F)
—
—
—
—
—
—
h
06
0.5°C (0.9°F)
h
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
h
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
h
03
–1°C (–1.8°F)
h
h
h
—
—
—
h
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
h
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
h
—
: Available
: Not available
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
3
01
Standard
02
Slightly increased
03
Increased
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...