SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
148
Note(s)
Note(s)
The control is automatically switched to the one performed only by the suction air thermistor for
indoor unit when the Second code No. is
01
during group control.
To use the
remote controller thermistor control during group control
, select the Second code
No.
02
in First code No.
6
.
: Factory setting
When the 10 (20)-6 setting is changed to
02
, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.3.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
Filter cleaning sign is not displayed when a self-cleaning decoration panel is mounted.
1.3.4 Information for intelligent Touch Manager/intelligent Touch Controller
: Factory setting
When field setting 10 (20)-6-
02
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10
(20)-2 has priority.
When field setting 10 (20)-6-
01
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10 (20)-6
has priority for group connection, and 10 (20)-2 has priority for individual connection.
1.3.5 Time for Absence Area Detection (For units with an infrared presence
sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time. Absent time defined for detection can be selected as follows:
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
10 (20)
6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
5
01
Only indoor unit sensor value (or remote controller sensor
value, if installed.)
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...