Part 4 Functions and Control
59
6. Protection Control
6.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
Cooling
The following control is performed in the entire system.
Heating
The following control is performed in the entire system.
Normal control
Pc > 3.55 MPa
High pressure standby
Reduce compressor capacity step
Pc > 3.72 MPa
Pc < 3.04 MPa
When occurring 3 times within 40
minutes, high pressure switch is
activated without high pressure standby,
thus outputting the error code
E3
.
Pc: High pressure sensor detection
value for each outdoor unit.
Normal operation
Pc > 3.04 MPa
High pressure standby
Reduce compressor capacity step
Pc > 3.72 MPa
Pc < 2.89 MPa
When occurring 3 times within 40
minutes, high pressure switch is
activated without high pressure standby,
thus outputting the error code
E3
.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...