Operation Flowchart
SiME332106E
50
Part 4 Functions and Control
Note(s)
1. Operation Flowchart
For detailed description of each function in the flow below, refer to the details on related function
on the following pages.
1. If the indoor unit stops or the thermostat turns OFF while in oil return control or defrost
control, pump down residual operation is performed on completion of the oil return operation
or defrost control.
2. Not performed during cooling mode.
Stop control
(1) Abnormal shutdown
(2) When system is in stop control
Standby control
(1) Restart standby
(2) Crankcase heater control
Startup control
(include pressure equalization before startup)
(1) Cooling startup control
(2) Heating startup control
Normal control
(1) List of functions in normal control
(2) Compressor control
(3) Compressor capacity control
(4) Compressor step control
(5) Electronic expansion valve control
(6) Step control of outdoor unit fans
Protection control
(1) High pressure protection control
(2) Low pressure protection control
(3) Discharge pipe protection control
(4) Inverter protection control
(5) Heating operation prohibition
(6) Overload protection control
Thermostat ON
End of
startup
control
Abnormality
Thermostat OFF
Conditions met for oil return
Special control
(1) Pump down residual control
(note 2)
(2) Oil return control (note 1)
Conditions met for defrosting
(3) Defrost control (note 1)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...