Troubleshooting by Error Code
SiME332106E
246
Part 6 Service Diagnosis
5.55 Open Phase
Applicable
Models
RXYMQ4-6AYFK
Error Code
U1
Method of Error
Detection
The phase of each phase is detected by phase detection circuit and open phase is judged.
Error Decision
Conditions
When any phase is open phase.
Supposed
Causes
Abnormal supply voltage
Open phase
Defective inverter PCB
Troubleshooting
Power supply
harness
(3-phase, 4 wires) is
properly connected to
the terminal
block.
The fuse of the noise
filter PCB is blown out.
Power supply
voltage falls within
380 V to 415 V between
L1-L2, L2-L3 and
L3-L1.
The connectors
between the terminal
block, noise filter PCB and
inverter PCB are properly
connected.
Connect the harness properly.
Replace the inverter PCB. (A3P)
Replace the noise filter PCB (A2P) and
the inverter PCB (A3P).
NO
NO
YES
YES
Check the power supply for
abnormalities.
NO
YES
Connect the connectors properly.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...