SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
241
5.53 Refrigerant Shortage Warning (Heating)
Applicable
Models
RXYMQ4-6AYFK
Error Code
U0
Sub code: 06
Method of Error
Detection
Detects refrigerant shortage according to the difference between low pressure equivalent
saturation temperature and suction pipe temperature, opening degree of main electronic
expansion valve, or superheating operation.
Error Decision
Conditions
The following conditions are satisfied for 20 minutes or more.
Suction pipe temperature – Low pressure equivalent saturation temperature > 30°C
Opening degree of main electronic expansion valve (Y1E) > 480 pulses
Discharge pipe temperature > 125°C, or low pressure < 0.15 MPa and high pressure < 2.1
MPa simultaneously.
No abnormality is determined, and the operation continues.
Supposed
Causes
Refrigerant shortage and refrigerant clogging (wrong piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...