Refrigerant Circuit (Piping Diagrams)
SiME332106E
18
Part 2 Refrigerant Circuit
1.2
VRV
Indoor Unit
No. in piping
diagram
Name
Electric
symbol
Applicable model
Function
(1)
Electronic expansion valve
Y1E
All indoor units
Used for gas superheating degree
control while in cooling or subcooling
degree control while in heating.
(2)
Suction air thermistor
R1T
All indoor units
Used for thermostat control.
(3)
Indoor liquid pipe thermistor
R2T
All indoor units
Used for gas superheating degree
control while in cooling or subcooling
degree control while in heating.
(4)
Indoor gas pipe thermistor
R3T
All indoor units
Used for gas superheating degree
control while in cooling.
FXFSQ-AR
FXDQ-PD, FXDQ-ND
FXMQ-PB
FXMQ-AR
C: 4D121746
(1)
(3)
(4)
(2)
C: 4D115598B
(3)
(2)
(1)
(4)
(3)
(2)
(1)
(4)
C: 4D110285
C: 4D097585B
(2)
(1)
(3)
(4)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...