Troubleshooting by Error Code
Part 6 Service Diagnosis
195
Note(s)
5.23 Current Leakage Detection
Applicable
Models
RXYMQ4-6AYFK
Error Code
E2
Sub code: 01
Method of Error
Detection
Current leakage is detected in the earth leakage detection circuit. Error is detected on the
outdoor unit main PCB.
Error Decision
Conditions
When leakage current is detected.
Supposed
Causes
Earth fault
Defective wiring with the current sensor
Temporary liquid back or refrigerant stagnation
Troubleshooting
1. M1C
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Correct the wiring.
Normal
(Keep operating)
It is possibly caused by
temporary oil return or
refrigerant stagnation.
(Perform maintenance
during long-term
shutdown such as a
power outage.)
Check
if the
connection to the
current sensor (T1A) is
correctly wired.
NO
Replace the compressor.
(
1)
Defective compressor
insulation
YES
YES
Replace the corresponding
parts.
Defective
insulation of parts
other than the
compressor
YES
NO
NO
Turn OFF the power supply,
and then disconnect the
compressor lead wire.
Reconnect the wires, and
then reconnect the unit to the
power supply.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...