Troubleshooting by Error Code
SiME332106E
194
Part 6 Service Diagnosis
5.22 Outdoor Unit Main PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
E1
Method of Error
Detection
Abnormality is detected under the communication conditions in the hardware section between
the indoor unit and outdoor unit.
Error Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal.
Supposed
Causes
Defective outdoor unit main PCB
Disconnection of the inside/outside relay wires
Troubleshooting
Return to normal?
YES
External factor other than
error (for example, noise
etc.).
Connect the inside/outside
relay wires correctly.
Replace the outdoor unit
main PCB (A1P).
NO
NO
Check if
inside / outside
relay wires of outdoor
unit main PCB is
disconnected.
YES
Turn OFF the power once and
turn ON again.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...