Troubleshooting by Error Code
SiME332106E
172
Part 6 Service Diagnosis
5.8 Power Supply Voltage Abnormality
5.8.1 Power Supply Voltage Abnormality (FXMQ-PB)
Applicable
Models
FXMQ-PB
Error Code
A8
Method of Error
Detection
Error is detected by checking the input voltage of the fan motor.
Error Decision
Conditions
When the input voltage of fan motor is 150 V or less, or 386 V or more.
Supposed
Causes
Defective power supply voltage.
Defective connection on signal line.
Defective wiring.
Instantaneous power failure, others.
Troubleshooting
YES
There are
problems on the
condition of power supply
described above.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Correct any fault.
NO
NO
YES
Check and correct each wiring.
It is possible there was an
external cause, such as
brownout or instantaneous
power failure.
Check the condition of the power
supply.
(1) Check if power supply voltage is
220-240 V ± 10%.
(2) Check if there is power open
phase or defective wiring.
(3) Check if power supply voltage
unbalance is within 6 V.
A8
Reoccurrence of
error.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...