Field Settings for Outdoor Unit
SiME332106E
118
Part 5 Field Settings and Test Operation
2.6 Setting Mode (Mode 2)
2.6.1 How to Make Settings
Selection of setting items
Selection of setting conditions
Press and hold the
MODE (BS1)
button for 5 seconds or more to
enter setting mode.
Press the
RETURN (BS3)
button to
return to the initial state of setting
mode.
Press the
MODE (BS1)
button to
return to normal mode.
If you become unsure of how to
proceed, press the
MODE (BS1)
button and return to normal mode.
SEG1 SEG2 SEG3
Normal
Default
Normal
: hold 5 seconds
: BLINKS
: ON
: OFF
Legend Segment
MODE
BS1
MODE
BS1
RETURN
BS3
RETURN
BS3
RETURN
BS3
SET
BS2
SET
BS2
Press the
SET (BS2)
button to select
the setting condition you want.
Press the
RETURN (BS3)
button to
confirm.
Press the
SET (BS2)
button to
select any of the setting item listed
in the following table.
Press the
RETURN (BS3)
button to
confirm. The current state of setting
item blinks.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...