SiME332106E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
115
2.5 Monitor Mode (Mode 1)
In the monitor mode, information can be retrieved about settings related to performance,
addresses, number of units and actual operation data.
2.5.1 Retrieve data by using BS button on outdoor unit main PCB
Selecting monitoring item
SEG1 SEG2 SEG3
Normal
Normal
: hold 5 seconds
: BLINKS
: ON
: OFF
Legend Segment
MODE
BS1
MODE
BS1
RETURN
BS3
RETURN
BS3
SET
BS2
Checking for description of data
Press the
SET (BS2)
button to select
any of the monitoring item listed in the
following table.
Press the
RETURN (BS3)
button to
confirm.
The current state of monitoring item will
appear on the 7 segment display.
Press the
MODE (BS1)
button to return
to normal mode.
Press the
RETURN (BS3)
button to
return to the initial state of monitor mode.
If you become unsure of how to
proceed, press the
MODE (BS1)
button and return to normal mode.
To enter monitor mode, press the
MODE (BS1)
button while in
normal mode.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...