Field Settings for Indoor Unit
SiME332106E
102
Part 5 Field Settings and Test Operation
Note(s)
1.4.24 Swing Pattern Settings
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed
side by side are set to swing in an opposite direction to agitate airflow to reduce temperature
irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.4.25 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
to
02
or
03
.
1.4.26 Setting of Static Pressure Selection
FXDQ-PD, FXDQ-ND
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
FXFSQ-AR, FXAQ-AR
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
4
01
Draft prevention (Upward)
02
Standard
03
Ceiling soiling prevention (Downward)
Model
No.
First Code
No.
Second
Code No.
Contents
13 (23)
5
01
Standard (10 Pa)
02
High static pressure (30 Pa)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...