SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
65
3.16
Gas Shortage Warning
Generates a warning when an excessive gas shortage occurs. This function generates an alarm only, and
does not stop operation.
• In cooling mode
· Lp < 0.10MPa (-21.6˚C) 30 continuous minutes
→
Outputs gas shortage warning [U0].
· Lp
≥
0.10MPa (-21.6˚C)
→
Cancels gas shortage warning.
• In heating mode
&
SH1 (Evaporator1 outlet
superheat degree) > 20˚C
Left conditions
remain for 60
continuous minutes
→
Outputs gas shortage warning [U0].
EV1 = 2000 pls (full open)
SH2 (Evaporator2 outlet
superheat degree) > 20˚C
EV2 = 2000 pls (full open)
SH3 (Evaporator3 outlet
superheat degree) > 20˚C
EV3 = 2000 pls (full open)
OR
SH1 (Evaporator1 outlet
superheat degree)
≤
20˚C
→
Cancels gas shortage warning.
EV1 < 2000 pls (full open)
SH2 (Evaporator2 outlet
superheat degree)
≤
20˚C
EV2 < 2000 pls (full open)
SH3 (Evaporator3 outlet
superheat degree)
≤
20˚C
EV3 < 2000 pls (full open)