Outline of Control (Outdoor Unit)
SiE 00-07
64
Function R-407C PLUS Series
3.15
Crankcase Heater Control
Controls the crankcase heater to prevent refrigerant from remaining in the inverter compressor.
Note:
STD compressor crankcase heater is controlled previous way. (ON/OFF by magnetic switch)
Crank case
heater OFF
Crank case heater
ON
• Outdoor air temp. > 30˚C
• Compressor ON
(V0833)
•
Outdoor air temp. < 27 ˚C
&
OR
OR
•
Compressor stop during
the magnet contactor of
INV compressor ON
•
The magnet contactor of
INV compressor OFF