SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
63
3.14
Inverter Protection Control
Controls the compressor upper-limit frequency to prevent tripping by inverter overcurrent and fin
temperature increase.
Raising upper limit
frequency for 1-step
Normal operation
Lowering upper limit
frequency for 1-step
(V0832)
•
Inverter current > 28
+3
-0
A
•
INV fin temp. > 92˚C
OR
•
Inverter current
≤
28
+3
-0
A
•
INV fin temp. < 87˚C
•
3-min elapse
OR
(every 10 sec)
(every 3 min)