Troubleshooting
SiE 00-07
154
Troubleshooting R-407C PLUS Series
3.32
Excessive Number of Indoor Units
Remote Controller
Display
UA
Supposed Causes
Excess of connected indoor units
Defect of outdoor unit PC board (A1P)
Troubleshooting
The number of indoor units that can be connected to a single outdoor unit system depends on the type of
outdoor unit.
∗
RSXYP16~20KJY1 ··· 20 units
RSXYP24~30KJY1 ··· 32 units
(VF059)
The total
of indoor units
displaying "UA" and indoor
units connected to the same
refrigerant system is
20 or 32 units or
less.
∗
Replace outdoor unit PC board (A1P).
Normal
NO
NO
There are too many indoor units within
the same refrigerant system.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
YES
YES
Does a malfunction occur?
Содержание VRV R-407C PLUS Series
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Страница 11: ...Introduction SiE 00 07 x...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...