Troubleshooting
SiE 00-07
138
Troubleshooting R-407C PLUS Series
3.16
Outdoor Unit: Actuation of Low Pressure Sensor
Remote Controller
Display
E4
Supposed Causes
Abnormal drop of low pressure (0 kg/cm
²
[0 MPa])
Defect of low pressure sensor
Defect of outdoor unit PC board
Troubleshooting
∗
1: Voltage measurement point
∗
2: Refer to pressure sensor, pressure / voltage characteristics table on P204.
(VF042)
Low pressure
at stop due to malfunction is
0.0 MPa.
Measure
the voltage (VL)
of X21A pin No. (2) - (3)
of outdoor PC board (A1P).
∗
1
Is the relationship
between low voltage
and VL
normal?
Out of gas, refrigerant system clogging,
wiring and piping wrong connection.
Replace the low pressure sensor.
Replace outdoor unit PC board A1P.
NO
NO
YES
YES