Piping installation
Installer and user reference guide
97
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
18.4.4 To charge refrigerant: Flow chart
98].
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2
• Open valves C and B to the liquid line
• Execute pre-charging amount: Q (kg)
Step 3a
• Close valves C and B
• Charging is finished
• Fill in the amount on the additional
refrigerant charge label
• Go to test run
Step 3b
Close valves C and B
R=Q
R>Q
R<Q
Continued on next page >>
p< p>
R410A
N2
C
A
B