19
|
Electrical installation
Installer and user reference guide
109
RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
Example
Combining the RWEYQ30T9 by using the RWEYQ8T9, RWEYQ10T9, and
RWEYQ12T9.
▪
Minimum circuit ampacity of the RWEYQ8T9=15.5 A
▪
Minimum circuit ampacity of the RWEYQ10T9=16.4 A
▪
Minimum circuit ampacity of the RWEYQ12T9=19.4 A
Accordingly, the minimum circuit ampacity of the
RWEYQ30T9=15.5+16.4+19.4=51.3 A
Multiply the above result by 1.1: (51.3 A×1.1)=56.43 A
⇒
the recommended fuse
capacity would be
63 A
.
NOTICE
When using residual current operated circuit breakers, be sure to use a high-speed
type 300 mA rated residual operating current.
19.2 To route and fix the transmission wiring
Transmission wiring can be routed through the front side only. Fix it to the upper
mounting hole.
A1P
F1
F1
F2
F2 Q1 Q2
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
A
A
Fix to the indicated plastic brackets (factory installed).
19.3 To connect the transmission wiring
The wiring from the indoor units must be connected to the F1/F2 (In‑Out)
terminals on the PCB in the outdoor unit.
Tightening torque for the transmission wiring terminal screws:
Screw size
Tightening torque (N•m)
M3.5 (A1P)
0.8~0.96