Field Setting from Remote Controller
Field Setting
90
(11) Compensating the Floor Temperature
(When the unit is equipped with an infrared floor sensor)
Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used to
have the actual floor temperature detected when, for example, the unit is installed close to a wall.
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed in the following cases:
(12) Optional Accessories Output Selection
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is output
between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
(13) External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input is performed
from the T1-T2 terminal of the operation terminal block in the el. compo. box.
Mode No.
First Code No.
Second Code
No.
Contents
11 (21)
9
01
–4°C (–7.2°F)
02
–2°C (–3.6°F)
03
0°C (0°F)
04
2°C (3.6°F)
Environment
Operation Mode
Problem
Setting Value
· The unit is installed close to a wall or a window.
· High thermal capacity of the floor whose material is
concrete, etc.
· There are many heat sources like a PC.
· There is a non-negligible heat source such as floor
heating.
Heating
Heated too much
2°C
(3.6°F)
Heated little
–2°C or –4°C
(–3.6°F or –7.2°F)
Mode No.
First Code No.
Second Code
No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with "Start/Stop" of remote controller is provided.
04
In case of "Error Display" appears on the remote controller, output
is provided.
05
—
06
—
07
Only for FXMQ-PB
Economizer (field supply) ON/OFF signal is provided.
F2 T1 T2
Forced OFF
Input A
Mode No.
First Code No.
Second Code
No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The
other indoor units indicate
U9
.
04
—
05
Only for FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
Содержание VRV IV-S RXTQ-TAVJU Series
Страница 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Страница 253: ...SiUS331604E Wiring Diagrams Appendix 240 1 Wiring Diagrams 1 1 Outdoor Unit RXTQ36TAVJU 3D100495A...
Страница 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Страница 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Страница 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Страница 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Страница 269: ...SiUS331604E Wiring Diagrams Appendix 256 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Страница 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...