9 Technical data
Installation and operation manual
32
8T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1B – 2016.04
Main code
Sub code
Cause
Solution
▪ Auto address malfunction (inconsistency)
▪ Mismatch of compressor unit and heat
exchanger unit.
▪ Check if transmission wired unit amount
matches with powered unit amount (by monitor
mode) or wait till initialisation is finished.
▪ Check if the compressor unit and heat
exchanger unit are compatible.
▪ The stop valves of the compressor unit are left
closed.
▪ The piping and wiring of the specified indoor unit
or heat exchanger unit are not connected
correctly to the compressor unit.
▪ Open the stop valves on both the gas and liquid
side.
▪ Confirm that the piping and wiring of the
specified indoor unit or heat exchanger unit are
connected correctly to the compressor unit.
9
Technical data
Latest information can be found in the technical engineering data.
9.1
Piping diagram: Compressor unit
and heat exchanger unit
5 HP
R2T
R3T
R1T
M1F
M2F
Y1E
Y3E
R2T
M1C
R3T
R7T
R4T
Y1S
S1NPL
S1PH
S1NPH
R5T
f
f
l
c
b
f
g
a
d
f
h
f
i
j
k
e
B
A
3D098825-1A
A
Heat exchanger unit
B
Compressor unit
a
Stop valve (gas) (circuit 2: to indoor units)
b
Stop valve (liquid) (circuit 2: to indoor units)
c
Stop valve (liquid) (circuit 1: to heat exchanger unit)
d
Stop valve (gas) (circuit 1: to heat exchanger unit)
e
Service port (refrigerant charge)
f
Filter
g
Subcool heat exchanger
h
Pressure regulating valve
i
Capillary tube
j
Accumulator
k
Compressor accumulator
l
Heat exchanger
M1C
Compressor
M1F, M2F
Fan motor
R1T (A)
Thermistor (air)
R2T (A)
Thermistor (gas)
R3T (A)
Thermistor (coil)
R2T (B)
Thermistor (discharge)
R3T (B)
Thermistor (suction accumulator)
R4T (B)
Thermistor (subcool heat exchanger gas)
R5T (B)
Thermistor (suction compressor)
R7T (B)
Thermistor (liquid)
S1NPH
High pressure sensor
S1NPL
Low pressure sensor
S1PH
High pressure switch
Y1E, Y3E
Electronic expansion valve
Y1S
Solenoid valve (4‑way valve)
Heating
Cooling
8 HP
Y2E
R21T
M1C
R3T
R5T
R6T
Y1S
S1NPL
S1PH
S1NPH
R7T
c
b
f
g
a
d
f
h
f
i
j
e
B
k
f
i
R2T
R3T
R1T
M1F
M2F
Y1E
M3F
f
f
l
A
3D104510-1
A
Heat exchanger unit
B
Compressor unit
a
Stop valve (gas) (circuit 2: to indoor units)
b
Stop valve (liquid) (circuit 2: to indoor units)
c
Stop valve (liquid) (circuit 1: to heat exchanger unit)
d
Stop valve (gas) (circuit 1: to heat exchanger unit)
e
Service port (refrigerant charge)
f
Filter
g
Subcool heat exchanger
h
Pressure regulating valve
i
Capillary tube
j
Accumulator
k
Oil separator