Si37-701
Example of Connection (R-410A Type)
Appendix
413
6. Example of Connection (R-410A Type)
Example of connection
(Connection of 8 indoor units)
Outdoor unit
side
(3 pipes)
Indoor unit
side
(2 pipes)
Suction gas pipe
HP/LP gas pipe
Liquid pipe
Gas pipe
Liquid pipe
BS
Unit
Suction gas pipe
HP/LP gas pipe
Liquid pipe
(Suction) gas pipe
Liquid pipe
Piping from outdoor unit to BS unit
Piping from BS unit to indoor unit or
Piping from Refrigerant branch kit to
indoor unit used as cooling only
(Bold):3 pipes
(Thin):2 pipes
(*1) " " Indicate the Outdoor unit multi
connection piping kit.
(*2) In case of multi outdoor system, re-read
"outdoor unit" to "the first Outdoor unit
multi connection piping kit" as seen from
the indoor unit.
Branch with REFNET joint
Branch with REFNET joint and header
Branch with REFNET header
Single
outdoor
system
REYQ
8~16
Multi
outdoor
system
REYQ
18~48
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
REFNET joint (A~G)
REFNET joint (A~G)
B1 ~ B4
: BS Unit
1 ~ 6
: Indoor unit (Cool/Heat selection possible)
7 , 8
: Indoor unit (Cooling only)
REFNET joint (A~G)
REFNET header
REFNET header
First outdoor unit multi connection piping kit
REFNET joint (A~G)
REFNET header
REFNET header
Maximum
allowable
length
Allowable
height
difference
Allowable length after the branch
Between outdoor unit (*2)
and indoor unit
Between first outdoor unit multi
connection piping kit and outdoor unit
(in case of multi system)
Between outdoor and indoor units
Between indoor and indoor units
Between outdoor and outdoor units
Actual pipe
length
Equivalent
length
Actual and
Equivalent
pipe length
Actual pipe
length
Difference in height
Difference in height
Difference in height
Total extention length
Pipe length between outdoor unit (*2) and indoor unit
≤
165m
Example 8 : a + b + c + d + e + s
≤
165m
Example 6 : a + b +
≤
165m, 8 : a + m + n + p
≤
165m Example 8 : a + o
≤
165m
Equvalent pipe length between outdoor unit (*2) and indoor unit
≤
190m (Note 1)
(Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100, 160 to be 4m, that of BSVQ250 to be 6m for calculation purposes)
Total piping length from outdoor unit (*2) to all indoor unit
≤
1000m
Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit
≤
10m
Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit
≤
13m
Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit
≤
40m (Note 2)
Example 8 : b + c + d + e + s
≤
40m
Difference in height between outdoor unit and indoor unit (H1)
≤
50m (Max 40m if the outdoor unit is below)
Difference in height between adjacent indoor units (H2)
≤
15m
Difference in height between adjacent outdoor units (H3)
≤
5m
Outdoor unit
r
≤
10m
(Equivalent length
≤
13m)
u + s
≤
10m
(Equivalent length
≤
13m)
u + t
≤
10m
(Equivalent length
≤
13m)
Example 6 : b +
≤
40m, 8: m + n + p
≤
40m
Example 8 : o
≤
40m
a
b
c
d
e
a
b
c
d
e
H1
H1
H1
H2
s
r
p
n
f
k
i
f
k
i
q
o
m
p
n
q
o
m
g
G
F
j
A
B
C
D
E
H1
S
r
A
B
C
D
E
B1
B2
B3
B4
1
2
3
4
5
6
7
8
H2
g
G
F
1
2
3
4
5
6
7
8
B1 ~ B5
: BS Unit
1 ~ 4 , 7 , 8
: Indoor unit (Cool/Heat selection possible)
5 , 6
: Indoor unit (Cooling only)
B1 ~ B4
: BS Unit
1 ~ 6
: Indoor unit (Cool/Heat selection possible)
7 , 8
: Indoor unit (Cooling only)
B1 ~ B4
: BS Unit
1 ~ 6
: Indoor unit (Cool/Heat selection possible)
7 , 8
: Indoor unit (Cooling only)
B1 ~ B5
: BS Unit
1 ~ 4 , 7 , 8
: Indoor unit (Cool/Heat selection possible)
5 , 6
: Indoor unit (Cooling only)
B1 ~ B4
: BS Unit
1 ~ 6
: Indoor unit (Cool/Heat selection possible)
7 , 8
: Indoor unit (Cooling only)
a
a
m
m
c
d
e
f
g
h
i
j
k
o
n
A
A
B
H2
B1
B2
B3
B4
B5
1
2
3
4
5
6
7
8
H3
r
t
s
H3
H3
r
t
s
a
b
c
d
e
f
h
k
o
B
8
H2
u
r
t
s
a
u
B1
B2
B3
B4
1
2
3
4
5
6
7
B5
b
c
d
e
m
p
p
n
b
g
h
i
j
k
f
d
b
h
j
f
o
n
H2
H1
H1
B1
B2
B3
B4
B5
B6
B1
B2
B3
B4
B5
B6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
c
e
m
g
i
k
o
n
H2
r
t
s
u
g
i
j
Содержание VRV III REYQ8PY1
Страница 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Страница 59: ...Specifications Si37 701 48 Specifications...
Страница 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Страница 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Страница 373: ...Piping Diagrams Si37 701 362 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12PY1 3D058154A S1NPH S2NPL...
Страница 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Страница 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Страница 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Страница 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Страница 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Страница 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Страница 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Страница 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Страница 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Страница 388: ...Si37 701 Wiring Diagrams for Reference Appendix 377 2 2 Field Wiring REYQ8P 10P 12P 14P 16PY1 3D057764...
Страница 389: ...Wiring Diagrams for Reference Si37 701 378 Appendix REYQ18P 20P 22P 24P 26P 28P 30P 32PY1 3D057762...
Страница 390: ...Si37 701 Wiring Diagrams for Reference Appendix 379 REYQ34P 36P 38P 40P 42P 44P 46P 48PY1 3D057763...
Страница 391: ...Wiring Diagrams for Reference Si37 701 380 Appendix 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 393: ...Wiring Diagrams for Reference Si37 701 382 Appendix FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Страница 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Страница 400: ...Si37 701 Wiring Diagrams for Reference Appendix 389 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561B...
Страница 401: ...Wiring Diagrams for Reference Si37 701 390 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Страница 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 404: ...Si37 701 Wiring Diagrams for Reference Appendix 393 FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206D...
Страница 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Страница 423: ...Piping Installation Point Si37 701 412 Appendix...
Страница 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Страница 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Страница 447: ...Si37 701 iv Index...
Страница 451: ...Si37 701 viii Drawings Flow Charts...