Si37-701
Field Setting
Test Operation
191
No.
Setting item
Description
0
Digital pressure
gauge kit display
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2
Low noise/demand
address
Address for low noise/demand operation
3
Test operation
settings
Used to conduct test operation without making changes
to the PC board and replacing the refrigerant, after the
completion of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
(Forced thermostat ON)
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
11
Sequential
operation setting
Sets sequential operation
(Factory set to ON)
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
18
High static pressure
setting
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
(In order to mount the diffuser duct, remove the cover
from the outdoor unit fan.)
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant recovery/
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22
Night-time low
noise setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
24
ENECUT test
operation
Used to forcedly turn ON the ENECUT. (Be noted that the
ENECUT is only functional with outdoor unit in the
stopped state - Japanese domestic model only.)
25
Setting of external
low noise level
Sets low noise level when the low noise signal is input
from outside.
26
Night-time low
noise operation
start setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low
noise operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
30
Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
b. “Setting mode 2”
<Selection of setting items>
<Selection of setting conditions>
Push and hold the MODE (BS1)
button for 5 seconds and set to
“Setting mode 2”.
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
Push the SET (BS2) button and set
to the setting condition you want.
↓
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of “Setting
mode 2”.
∗
If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
(V2764)
Содержание VRV III REYQ8PY1
Страница 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Страница 59: ...Specifications Si37 701 48 Specifications...
Страница 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Страница 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Страница 373: ...Piping Diagrams Si37 701 362 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12PY1 3D058154A S1NPH S2NPL...
Страница 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Страница 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Страница 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Страница 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Страница 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Страница 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Страница 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Страница 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Страница 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Страница 388: ...Si37 701 Wiring Diagrams for Reference Appendix 377 2 2 Field Wiring REYQ8P 10P 12P 14P 16PY1 3D057764...
Страница 389: ...Wiring Diagrams for Reference Si37 701 378 Appendix REYQ18P 20P 22P 24P 26P 28P 30P 32PY1 3D057762...
Страница 390: ...Si37 701 Wiring Diagrams for Reference Appendix 379 REYQ34P 36P 38P 40P 42P 44P 46P 48PY1 3D057763...
Страница 391: ...Wiring Diagrams for Reference Si37 701 380 Appendix 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 393: ...Wiring Diagrams for Reference Si37 701 382 Appendix FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Страница 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Страница 400: ...Si37 701 Wiring Diagrams for Reference Appendix 389 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561B...
Страница 401: ...Wiring Diagrams for Reference Si37 701 390 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Страница 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 404: ...Si37 701 Wiring Diagrams for Reference Appendix 393 FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206D...
Страница 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Страница 423: ...Piping Installation Point Si37 701 412 Appendix...
Страница 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Страница 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Страница 447: ...Si37 701 iv Index...
Страница 451: ...Si37 701 viii Drawings Flow Charts...