Special Control
Si37-701
116
Function
3.3.2 Heating Oil Return Operation (including cooling / heating
simultaneous operation)
[Start conditions]
Referring to the following conditions, start heating oil return operation.
• Integral oil rise rate is reached to specified level.
• When cumulative compressor operating time exceeds 8 hours (2 hours when the power supply turns ON for
the first time)
Furthermore, the integral oil rise rate is calculated by Tc, Te, and compressor loads.
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the "Oil returning" process.
(Non-operating units stop while in "Preparation" mode.)
Actuator
Symbol
Elect. symbol
Oil return operation
REYQ
REMQ
Compressor 1
—
M1C
M1C
Maintain load that was applied before oil return
operation.
When current circulation rate < circulation rate required
for oil return operation, turn ON the STD compressor
every 10 seconds (up to 3 units at maximum).
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
When outdoor unit heat exchanger is condenser, the
fan will run under cooling fan control.
When outdoor unit heat exchanger is evaporator, the
fan will run at the fan step 7 or 8.
Outdoor unit fan 2
M2F
M2F
Electronic expansion valve (main)
EVM
Y1E
Y3E
Y1E
20SA=ON : PI control
20SA=OFF : 418pls
Electronic expansion valve
(subcooling)
EVT
Y2E
Y5E
Y3E
PI control
Electronic expansion valve (refilling
refrigerant)
EVJ
Y4E
Y2E
80pls
Four way valve (for heat changer
selection)
20SA
Y2S
Y9S
Y3S
When outdoor unit heat exchanger is condenser, the
valve will turn OFF.
When outdoor unit heat exchanger is evaporator, the
valve will turn ON.
Four way valve (for high- and low-
pressure gas pipe selection)
20SB
Y8S
Y2S
OFF
Solenoid valve (main bypass)
SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (hot gas)
SVP
Y4S
Y5S
0pls
Solenoid valve (liquid pipe of
refrigerant regulator)
SVL
Y3S
Y4S
0pls
Solenoid valve (gas discharge pipe of
refrigerant regulator)
SVG
Y1S
Y1S
0pls
Solenoid valve (drain pipe of
refrigerant regulator)
SVO
Y7S
Y7S
0pls
Solenoid valve (discharge pipe of
refrigerant regulator)
SVT
Y6S
Y8S
0pls
End conditions
•
Pe_min<0.22MPa
•
After a lapse of 9 min.
OR
or
Содержание VRV III REYQ8PY1
Страница 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Страница 59: ...Specifications Si37 701 48 Specifications...
Страница 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Страница 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Страница 373: ...Piping Diagrams Si37 701 362 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12PY1 3D058154A S1NPH S2NPL...
Страница 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Страница 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Страница 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Страница 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Страница 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Страница 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Страница 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Страница 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Страница 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Страница 388: ...Si37 701 Wiring Diagrams for Reference Appendix 377 2 2 Field Wiring REYQ8P 10P 12P 14P 16PY1 3D057764...
Страница 389: ...Wiring Diagrams for Reference Si37 701 378 Appendix REYQ18P 20P 22P 24P 26P 28P 30P 32PY1 3D057762...
Страница 390: ...Si37 701 Wiring Diagrams for Reference Appendix 379 REYQ34P 36P 38P 40P 42P 44P 46P 48PY1 3D057763...
Страница 391: ...Wiring Diagrams for Reference Si37 701 380 Appendix 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 393: ...Wiring Diagrams for Reference Si37 701 382 Appendix FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Страница 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Страница 400: ...Si37 701 Wiring Diagrams for Reference Appendix 389 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561B...
Страница 401: ...Wiring Diagrams for Reference Si37 701 390 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Страница 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 404: ...Si37 701 Wiring Diagrams for Reference Appendix 393 FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206D...
Страница 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Страница 423: ...Piping Installation Point Si37 701 412 Appendix...
Страница 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Страница 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Страница 447: ...Si37 701 iv Index...
Страница 451: ...Si37 701 viii Drawings Flow Charts...