Field Setting
SiBE37-701
202
Test Operation
3.2
Field Setting from Outdoor Unit
3.2.1
Field Setting from Outdoor Unit
List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1, and Setting mode 2, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on page 219 onward.
Setting item
Content and objective of setting
Overview of setting procedure
Reference
page
F
u
nct
ion
se
tt
in
g
2
Setting of low
noise
operation (*1)
A. Use external input to step down the upper
limit of the fan (factory set to Step 8),
providing low noise level.
(1) Mode 1: Step 5 or lower
(2) Mode 2: Step 4 or lower
(3) Mode 3: Step 3 or lower
Use the "External control adaptor for
outdoor unit".
Set to "External control adaptor for
outdoor unit" with No. 12 of "Setting mode
2" and select the mode with No. 25.
If necessary, set the "Capacity priority
setting" to ON with No. 29.
B. The low noise operation aforementioned
is enabled in nighttime automatic low
noise operation mode.
Start time: Possible to select in the range
of 20:00 to 24:00 hours.
End time: Possible to select in the range
of 06:00 to 08:00 hours.
(Use the said time as a guide since the
start time and the end time are estimated
according to outdoor temperatures.)
Make this setting while in "Setting mode
2".
Select a mode with No. 22 of "Setting
mode 2".
Select the start time with No. 26 and the
end time with No. 27.
If necessary, set the "Capacity priority
setting" to ON with No. 29.
3
Setting of
demand
operation (*1)
Used to place limits on the compressor
operating frequency to control the upper
limit of power consumption.
(1) Mode 1 of Demand 1: 60% or less of
rating
(2) Mode 2 of Demand 1: 70% or less of
rating
(3) Mode 3 of Demand 1: 80% or less of
rating
(4) Demand 2: 40% or less of rating
For setting with the use of "external
control adapter":
Set the system to "External control
adaptor for outdoor unit" with No. 12 of
Setting mode 2" and select the mode with
No. 30.
For setting only in "Setting mode 2":
Set the system to Normal demand mode
with No. 32 of "Setting mode 2" and select
the mode with No. 30.
4
Setting of
AirNet
address
Used to make address setting with AirNet
connected.
Set the AirNet to an intended address
using binary numbers with No. 13 of
"Setting mode 2".
6
Setting of
high static
pressure
Make this setting to operate a system with
diffuser duct while in high static pressure
mode. (Use this setting mode when
shields are installed on upper floors or
balconies.)
* In order to mount the diffuser duct,
remove the cover from the outdoor unit
fan.
Set No. 18 of "Setting mode 2" to ON.
7
Prevention of
minute
heating
operation by
heating
thermostat
OFF unit or
non-heating-
operation unit
Make this setting to prevent a rise in room
temperature due to minute heating
capacity generated by heating thermostat
OFF unit or non-heating-operation unit
while in heating operation.
Set the Setting item No. 41 of “Setting
mode 2” to heating thermostat OFF unit or
non-heating-operation unit.
(Overseas unit: Default set to “ON”)
8
Setting of BS
Cool-Heat
selection
control time
Make this setting to shorten the BS Cool-
Heat selection control time.
Set the Setting item No. 42 of “Setting
mode 2” to “ON”.
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...