Protection Control
SiBE37-701
134
Function
4.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
[Contents]
★
The following control is performed for each compressor of single unit as well as multi units.
[INV compressor]
[STD compressor]
In control of discharge pipe temperature protection
INV Comp. upper
limit step:
1-step down
INV Comp. upper
limit step:
1-step up
HTdi>115˚C
or
HTdi>115˚C
Tp>135˚C
or
HTdi<100˚C
Tp<110˚C
HTdi>130˚C
or
HTdi>135˚C
HTdi>120˚C continues for 10 minutes or more.
or
After 30 sec.
After 20 sec.
Frequency agreement
Tp>135˚C
HTdi<110˚C
Tp<125˚C
&
&
52Hz+OFF+OFF
HTdi>120˚C continues for 90 seconds
or more.
When occuring 3 times within 100 min.,
the malfunction code “F3” is output.
Normal operation
INV upper limit step=max (Max. step)
Discharge pipe
temperature
standby
or
After 10 min.
Discharge pipe temp.
protection control not limited
HTds>120˚C continues for 5 min. or more.
HTds>135˚C
Tp>135˚C continues for 10 min. or more.
HTds : Value of STD compressor discharge
pipe temperature (
Tds) compensated
with outdoor air temperature
Tp :
Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.
Applicable STD
compressor stops.
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...