Special Control
SiBE37-701
126
Function
3.5
Pump-down Residual Operation
3.5.1 Pump-down Residual Operation in Cooling Operation
If the liquid refrigerant stays in the Evaporator at the startup of a compressor, this liquid refrigerant enters the
compressor, thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Consequently, in order to recover the refrigerant in the Evaporator while the compressor stops, the pump-down residual
operation is conducted.
*
Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
Actuator
Symbol
Elect.
symbol
Master unit operation
Slave unit operation
REYQ
REMQ
Compressor 1
—
M1C
M1C
124 Hz+OFF+OFF
OFF
Compressor 2
M2C
M2C
Compressor 3
M3C
M3C
Outdoor unit fan 1
—
M1F
M1F
Fan control
Fan control
Outdoor unit fan 2
M2F
M2F
Electronic expansion valve (Main) EVM
Y1E
Y3E
Y1E
1375 pls
1375 pls
Electronic expansion valve
(Supercooling)
EVT
Y2E
Y5E
Y3E
0 pls
0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
80 pls
Four way valve (Heat exchanger
switch)
20SA
Y2S
Y9S
Y3S
OFF
OFF
Four way valve (High/low pressure
gas pipe switch)
20SB
Y8S
Y2S
ON
ON
Solenoid valve (Main bypass)
SVE
Y5S
Y10S
Y6S
ON
ON
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
Solenoid valve (Refrigerant
regulator liquid pipe )
SVL
Y3S
Y4S
OFF
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
OFF
Solenoid valve (Refrigerant
regulator exhaust pipe)
SVO
Y7S
Y7S
OFF
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
Ending conditions
•
5 min.
•
Pe_min<0.49 MPa
∗
•
Pc_max<2.94 MPa
∗
•
Master unit Tdi>110
°
C
•
Master unit Tp>125
°
C
or
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...