Si39-303
Unpacking and Placing the Unit
Installation Manual
165
5. Unpacking and Placing the Unit
!
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and
noise.
!
Secure the unit to its base using foundation bolts. (Use four commercially available M12-
type foundation bolts, nuts, and washers.)
!
The foundation bolts should be inserted 20 mm.
!
Make sure the base under the unit extended more than 765mm behind the unit.
!
The height of the base should be at least 150mm from the floor.
!
The unit must be installed on a solid longitudinal foundation (steel beam frame
or concrete) as indicated in figure below.
1.Foundation bolt point (
φ
15 dia. : 4 positions)
2.Depth of product
3.Shape of indoor unit’s support leg and foundation bolt positions
Do not use stands to support the corners
Caution
1. Prepare a water drainage channel around the foundation to drain waste water from around
the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of
150mm under the unit in order to prevent infiltration of water coming from under the unit.
[Precaution]
!
When installing on a roof, make sure the roof floor is strong enough and be sure to water-
proof all work.
!
Make sure the area around the machine drains properly by setting up drainage grooves
around the foundation.
(Drain water is sometimes discharged from the outdoor unit when it is running.)
!
Block all gaps in the holes for passing out piping and wiring using sealing material (locally
procured). (Small animals may enter the machine.)
Model
AB
Q5 type
635
497
Q8 · 10 type
930
792
Q12 · 14 · 16 type
1240
1102
20
722-737
80
80
765
A
B
1
2
3
Do not use stands to
support the corners.
Содержание VRV II Series
Страница 6: ...Si39 303 iv Table of Contents...
Страница 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Страница 124: ...Appendix Si39 303 118 General Information 3P114237A...
Страница 130: ...Appendix Si39 303 124 General Information BHFP22M135 Refer P 120 for Table 7 8 and 9 After connection piping...
Страница 140: ...Appendix Si39 303 134 General Information 7 10 Piping System Diagrams 7 10 1 Outdoor Unit RXYQ5MY1B...
Страница 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Страница 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Страница 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Страница 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Страница 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Страница 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Страница 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Страница 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Страница 158: ...Appendix Si39 303 152 General Information...
Страница 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Страница 226: ...Troubleshooting Si39 303 220 Operation Manual...