Symptom-based Troubleshooting
Si39-504
154
Troubleshooting
1. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
Power failure
After the power failure is reset,
restart the system.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool or heat air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to "LOW"
Set it to a proper airflow rate.
Improper direction of air diffusion Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
[In cooling] Direct sunlight received
Hang curtains or shades on
windows.
[In cooling] Too many persons staying in a
room
[In cooling] Too many heat sources (e.g. OA
equipment) located in a room
4
The system does
not operate.
The system stops and
immediately restarts operation.
If the OPERATION lamp on the
remote controller turns ON, the
system will be normal. These
symptoms indicate that the
system is controlled so as not to
put unreasonable loads on the
system.
Normal operation. The system will
automatically start operation after
a lapse of five minutes.
Pressing the TEMP ADJUST
button immediately resets the
system.
The remote controller displays
"UNDER CENTRALIZED
CONTROL", which blinks for a
period of several seconds
when the OPERATION button
is depressed.
The system is controlled with
centralized controller. Blinking
display indicates that the system
cannot be operated using the
remote controller.
Operate the system using the
COOL/HEAT centralized remote
controller.
The system stops immediately
after turning ON the power
supply.
The system is in preparation
mode of micro computer
operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent
stops.
The remote controller displays
malfunction codes "U4" and
"U5", and the system stops but
restarts after a lapse of several
minutes.
The system stops due to an
interruption in communication
between units caused by
electrical noises coming from
equipment other than air
conditioners.
Remove causes of electrical
noises.
If these causes are removed, the
system will automatically restart
operation.
6
COOL-HEAT
selection is
disabled.
The remote controller displays
"UNDER CENTRALIZED
CONTROL".
This remote controller has no
option to select cooling operation.
Use a remote controller with
option to select cooling operation.
The remote controller displays
"UNDER CENTRALIZED
CONTROL", and the COOL-
HEAT selection remote
controller is provided.
COOL-HEAT selection is made
using the COOL-HEAT selection
remote controller.
Use the COOL-HEAT selection
remote controller.
ON
OFF
Knob
Tripped
Circuit breaker
Содержание VRV II RXYQ5MATL
Страница 20: ...Si39 504 Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Outdoor Units 10 1 2 Indoor Units 21...
Страница 53: ...Specifications Si39 504 42 Specifications...
Страница 56: ...Si39 504 Refrigerant Circuit Refirgerant Circuit 45 RXYQ5MA 3D048203 2 4 3 5 K J S E D M T N P A G O 1 W V...
Страница 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Страница 161: ...Field Setting Si39 504 150 Test Operation...
Страница 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Страница 265: ...Piping Diagrams Si39 504 254 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAYL E TL E 3D048203...
Страница 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Страница 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Страница 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Страница 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Страница 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Страница 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Страница 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Страница 277: ...Wiring Diagrams for Reference Si39 504 266 Appendix RXYQ18MA 20MA 22MA 24MA 26MA 28MA 30MA 32MAYL E 3D040747H...
Страница 278: ...Si39 504 Wiring Diagrams for Reference Appendix 267 RXYQ34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MAYL E C 3D040748H...
Страница 279: ...Wiring Diagrams for Reference Si39 504 268 Appendix 2 2 2 RXYQ MATL E RXYQ5MA 8MA 10MA 12MA 14MA 16MATL E 3D041990A...
Страница 280: ...Si39 504 Wiring Diagrams for Reference Appendix 269 RXYQ18MA 20MA 22MA 24MA 26MA 28MA 30MA 32MATL E 3D041991A...
Страница 281: ...Wiring Diagrams for Reference Si39 504 270 Appendix RXYQ34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MATL E 3D041992A...
Страница 282: ...Si39 504 Wiring Diagrams for Reference Appendix 271 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 284: ...Si39 504 Wiring Diagrams for Reference Appendix 273 FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Страница 286: ...Si39 504 Wiring Diagrams for Reference Appendix 275 FXDQ20N 25N 32N 40N 50N 63NVE with Drain Pump 3D045500C...
Страница 287: ...Wiring Diagrams for Reference Si39 504 276 Appendix FXDQ20N 25N 32N 40N 50N 63NVET without Drain Pump 3D049604A...
Страница 288: ...Si39 504 Wiring Diagrams for Reference Appendix 277 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Страница 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Страница 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Страница 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Страница 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Страница 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...